This page documents the 22C-B017H103, a PowerFlex 400 fan and pump drive. The number decodes position by position: 22C is the series, B fixes the 200...240 V AC three phase input, 017 is the rating code that sets 17.5 A and 3.7 kW (5 HP) in frame C, H is the enclosure (not printed in the 22C enclosure table), and 103, the standard build ending used at both voltages and every frame closes the number.
| Position | Value |
| 1-3 | 22C, PowerFlex 400 adjustable frequency drive for fan and pump applications |
| 4 | B, 200...240 V AC three phase |
| 5-7 | 017, 17.5 A output current and 3.7 kW (5 HP), frame C |
| 8 | H, not printed in the 22C enclosure table |
| 9-12 | 103, the standard build ending used at both voltages and every frame |
| Attribute | Value |
| Output current | 17.5 A |
| Motor rating | 3.7 kW (5 HP), variable torque fan and pump duty |
| Frame | C |
| Power terminal range, frame C | 8.4 mm2 (8 AWG) maximum, 1.3 mm2 (16 AWG) minimum, recommended torque 3.7 N.m (33 lb.in) |
| Input voltage | 200...240 V AC |
| Ambient, panel mount | 45 C (113 F) surrounding air, IP20 open and IP30 Type 1 |
A caution on this number: the published 22C catalog number explanation lists only N (IP20 open), A (IP30 Type 1) and F (flange) in the enclosure position, and H is not among them. The rating percentages attached to 17.5 A and 3.7 kW are unaffected, but the enclosure letter should be read off the unit nameplate rather than inferred from this page.
The published table places this rating between 012: 12.0 A, 2.2 kW (3 HP), frame C; 024: 24.0 A, 5.5 kW (8 HP), frame C. When a fan or pump is re-rated, these are the two numbers the drive is compared with, and the frame letter in each case tells you whether the terminal block changes along with the current.
Direct links to the neighbouring ratings in this voltage class: 22C-B012, 22C-B024.
The isolation transformer pairing is published. Each rating is paired in the publication with a 1321-3TW or 1321-3TH isolation transformer from 5 kVA to 390 kVA, with 208 V, 230 V, 460 V and 575 V primaries. On a corner grounded delta or an ungrounded system, that pairing is the published route to a drive input voltage the range was tested at, and it is cheaper than arguing about the supply afterwards.
Ambient is a cabinet number, not a drive number. The panel mount drives are published for a 45 C (113 F) surrounding air temperature, and that figure is measured inside the enclosure rather than in the plant. A fan or pump room at 35 C with an unventilated cabinet at 52 C is a drive running 7 C over its published ambient, and the remedy is airflow or the flange option, not a larger drive.
Frame e is two terminal blocks under one letter. Frame E covers 480 V 37...45 kW (50...60 HP) drives that take up to 8 AWG and 240 V 30...37 kW / 480 V 55...75 kW drives that take up to 4/0 AWG. Two drives with the same frame letter can therefore need different lugs and different cable, and the rating code rather than the frame is what tells them apart.
What the current figure does and does not cover. The output current in the table is the drive rating at the published ambient and switching conditions. Motor current on a fan varies with speed and air density, so a drive sized exactly to the motor nameplate can be short of current on a cold day at full speed; the margin is a design decision, and the table gives the ceiling it has to fit under.
Terminals follow ul, the installation code may not. Power terminals are sized according to UL, and the publication states that local or national codes may require a larger conductor than the terminal accepts, in which case multiple conductors, 90 C wire or lugs are used. The wire range in the frame table is a terminal limit; the run to the motor is a separate calculation done against the installation code in force.
Frame C in practice. Frame C is the frame that changes character with the enclosure code. It ships as IP20 open and reaches IP30 Type 1 only through a field installed conversion kit with a top cover and conduit box, and it is the only frame where flange mounting is available at the lower ratings. The terminal block takes up to 8 AWG at 3.7 N.m, so a 5 HP fan on a long run is a wire size question rather than a lug question.
What a quotation needs beyond the number. A drive number alone will not close a fan package: the panel needs the branch protection device, the installer needs the cable range, and the mechanical designer needs the heat figure. Each of those is published separately from the rating table, which is why a quotation built only from the catalog number tends to come back with three questions attached.
| Parameter | Value |
| Dimensions with base | 120 H x 72 W x 42 D mm (4.72 x 2.83 x 1.65 in.) for I/O modules; 112 H x 72 W x 65 D mm (4.41 x 2.83 x 2.56 in.) for the DeviceNet adapters |
| Enclosure rating | Meets IP65/66/67 when marked; the sealed housing needs no cabinet, though a plant with washdown or corrosive atmosphere can still require one |
| Operating temperature | -20 to 60 degrees C (-4 to 140 degrees F), IEC 60068-2-1 cold, 60068-2-2 dry heat and 60068-2-14 thermal shock |
| Storage temperature | -40 to 85 degrees C (-40 to 185 degrees F) |
| Relative humidity | 5 to 95 percent non-condensing, IEC 60068-2-30 damp heat |
| Shock and vibration | Operating 30 g, non-operating 50 g; 5 g at 10-500 Hz operating |
| Isolation | 50 V rms continuous withstand, tested at 1,250 V ac rms for 60 s |
| ESD and RF immunity | 6 kV contact and 8 kV air discharge, 10 V/m radiated RF from 30 MHz to 2,000 MHz, 10 Vrms conducted RF from 150 kHz to 80 MHz |
| Transient immunity | Plus or minus 3 kV at 5 kHz EFT on signal ports, plus or minus 1 kV line-to-line and plus or minus 2 kV line-to-earth surge |
| Emissions | CISPR 11 Group 1 Class A |
| Mounting | Mounted on a grounded metal plate with #8 (M4) screws; base torque 7.5 in-lb in aluminium and 16 in-lb in steel; the ground lug is also a mounting hole |
| Weight | 0.29 kg (0.64 lb) with base |
| Field power bus | 24 V dc nominal, 10 to 28.8 V dc range |
| PointBus current | 75 mA at 5 V dc for digital and analog modules, 110 mA for 1738-SSIM23 |
Connector shells are the part of the ordering decision a drawing rarely shows. M8 is a single-pin pico shell, M12 is a four or five pin micro shell, M23 is a twelve pin shell, and the same channel count can be delivered in three different shell sizes with three different cable preparations. A plant that standardises on M12 cord sets buys the M12 variant; a plant that already runs M8 patch cables buys the M8 variant and gets the same eight channels in eight single-pin shells, and the field wiring effort differs accordingly.
ArmorPoint modules are installed by bridging two bases, which is why every mechanical figure in this family is stated with the base included rather than for the module alone.
Figures on this page are the published 22C technical data for this catalog number. Where a value is not printed in that publication it is not printed here either, and no price, lead time or lifecycle statement is implied.
Twelve of the 47 22C records carried on this site, ordered by how close their codes sit to this one. This page is 22C-B017H103.
This listing is filed in the AB Drives & Motors group on plc-vip.com; the group index is AB Drives & Motors catalogue index, and the 22C-B017H103 page is one entry in it.
Sources. Rockwell publishes the PowerFlex 400 user manual as 22C-UM001 and the technical data for the family as 22C-TD001. The ratings, terminal designations and ordering characters quoted on this page for 22C-B017H103 follow those two publications.