|
Product Details:
Payment & Shipping Terms:
|
22CB012H103 is an Allen-Bradley PowerFlex 400 drive for fan and pump duty: 240 V AC, three phase, 12 A output, 2.2 kW / 3.0 HP, frame C.
The 400 range covers 2.2 to 37 kW at 240 V and 2.2 to 250 kW at 480 V, and the drive is built around variable torque loads, so the ratings below are the fan and pump ones.
Quick answer. 22CB012H103 is a Rockwell Automation Allen-Bradley PowerFlex 400 drive, 240 V AC, normal duty, frame C.
| 22CB012F103 | 2.2 kW / 3.0 HP | IN STOCK |
| 22CB012H103 | 2.2 kW / 3.0 HP | IN STOCK |
| 22CB012N103 | 2.2 kW / 3.0 HP | IN STOCK |
| 22CB017F103 | 3.7 kW / 5.0 HP | IN STOCK |
| 22CB017H103 | 3.7 kW / 5.0 HP | IN STOCK |
| 22CB017N103 | 3.7 kW / 5.0 HP | IN STOCK |
| 22CB024H103 | 5.5 kW / 7.5 HP | IN STOCK |
| 22CB024N103 | 5.5 kW / 7.5 HP | IN STOCK |
| 22CB033F103 | 7.5 kW / 10 HP | IN STOCK |
| 22CB033H103 | 7.5 kW / 10 HP | IN STOCK |
| 22CB033N103 | 7.5 kW / 10 HP | IN STOCK |
Catalog number |
22CB012H103 |
Voltage rating (b) |
B - 240 V AC, three phase |
Output current rating (c) |
12 A |
Power rating |
2.2 kW / 3.0 HP |
Frame size |
C |
Enclosure (d H) |
Enclosure letter H as ordered - 22C-TD001 lists N, A and F only, so confirm on the nameplate |
Interface module (e 1) |
Fixed keypad |
Emission class (f 0) |
not filtered |
Version (g 3) |
RS485 |
Rating code |
012 - output current in amps |
Source |
22C-TD001 Catalog Number Explanation, tables c1 (240 V) and c2 (480 V) |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 22C-TD001 (module specifications) and 22C-UM001 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
22C is the PowerFlex 400 family; position b is the voltage class, here 240 V AC, three phase.
Positions 6 to 8 are the output current code, 012, which reads as 12 A.
Position d is the enclosure, e the interface module (the field drive ships with the fixed keypad), f the emission class - 0 means not filtered - and g the version, 3 being RS485.
At 240 V AC, three phase the drive delivers 12 A continuous at 2.2 kW (3.0 HP) on variable torque fan and pump load.
Enclosure d=N is the panel mount IP20 open drive; frame C drives are only offered with IP20 open, and a field installed conversion kit is needed to reach the IP30 NEMA/UL Type 1 rating.
Built-in features for air handlers and pumps include PID, sleep/wake, pipe fill, damper control, purge and fire/freeze inputs, plus skip frequency bands that keep a fan out of a resonant speed.
Built-in features aimed at air handlers and pumps include the PID loop, sleep/wake control, pipe fill, a damper and purge routine, and the skip frequency bands that keep a fan out of a resonant speed.
d=F is the flange mount, offered on frame C only, for heat sink through panel mounting.
d=F is the flange mount, offered on frame C only, for heat sink through panel mounting.
Frame D and larger ratings normally ship as d=A, the IP30 NEMA/UL Type 1 enclosure, with an unfiltered drive (f=0) needing an external filter or a filtered enclosure to meet the site emission limits.
The frame (C, D, E or F) because it decides terminal wire range - frame C accepts 8 AWG, frame D 2 AWG, frame E and above 4/0 AWG or larger.
The enclosure letter against the installed environment, since an IP20 open drive inside a washdown area is the wrong build.
Whether the application is really variable torque; the 400 is a fan and pump drive, and a constant torque load should be sized on a different family.
Voltage classes, current codes, kW and HP values, frame sizes and enclosure letters are transcribed from 22C-TD001: Catalog Number Explanation and the 200-240 V and 380-480 V rating tables.
Feature statements - PID, sleep/wake, pipe fill, purge, skip frequencies, variable torque sizing - come from the product description and feature list in the same publication.
What is 22CB012H103?
Allen-Bradley PowerFlex 400 fan and pump drive, 240 V AC, three phase, 12 A, 2.2 kW / 3.0 HP, frame C.
What is the output current of 22CB012H103?
12 A at 240 V AC, three phase.
What power rating does 22CB012H103 have?
2.2 kW, 3.0 HP.
What frame size is 22CB012H103?
Frame C.
What enclosure does 22CB012H103 use?
Enclosure letter H as ordered - 22C-TD001 lists N, A and F only, so confirm on the nameplate.
Related catalog numbers in the same rating code. Same power stage, different option string - the enclosure, HIM, communication and safety positions are what change between them.
22CB012F103 (2.2 kW / 3.0 HP) · 22CB012N103 (2.2 kW / 3.0 HP) · 22CB017F103 (3.7 kW / 5.0 HP) · 22CB017H103 (3.7 kW / 5.0 HP) · 22CB017N103 (3.7 kW / 5.0 HP) · 22CB024H103 (5.5 kW / 7.5 HP) · 22CB024N103 (5.5 kW / 7.5 HP) · 22CB033F103 (7.5 kW / 10 HP) · 22CB033H103 (7.5 kW / 10 HP)
22C-B012H103 is a PowerFlex 400 adjustable frequency drive for fan and pump duty, documented here from the Rockwell user manual so that the rating, the frame, the enclosure and the EMC filter requirement are stated for this exact catalog number rather than for the family.
| Specification | Value |
|---|---|
| Catalog number | 22C-B012H103 |
| Voltage class | 200 to 240V AC, 3 phase |
| Output current | 12 A |
| Power rating | 2.2 kW, 3.0 HP |
| Frame | C |
| Enclosure code | H, position 9 of the catalog number; the current manual documents N, A and F only, so the H enclosure rating must be confirmed from the drive nameplate |
| Keypad | 1, fixed keypad |
| Emission class | 0, not filtered |
| Comm slot | 3, RS485 |
| External filter for EMC compliance | 22-RF034-CS |
| Restricted motor cable length with filter | 10 m (33 ft) |
| Source | 22C-UM001J-EN-E PowerFlex 400 user manual, ratings and catalog number explanation |
Twelve amps at 240 volts for 2.2 kW is the number that sizes everything downstream: the motor cable, the contactor, the overload and the filter. Comparing this unit with the 480 volt 2.2 kW drive by kW alone hides a factor of two in current.
Frame C is the small frame of the family, and the manual states that it is available only in the open type enclosure, with a field installed Option kit for the NEMA 1 rating. That kit is a panel decision, because it changes the clearances and the ambient limit at the same time.
Read the twelve characters before the datasheet: voltage class, rating, enclosure, keypad, emission class and communication slot are all encoded there, and the rating table converts the code into amps, kW, HP and frame. What the code does not say is how much filter and how much cable the installation will need, which is why the compliance tables belong in the specification rather than in an appendix.
Air temperature limits depend on mounting method, not only on enclosure rating. The open type frame accepts a higher ambient when it is mounted with the clearances for open ventilation, and a drive squeezed into a sealed cabinet loses that margin.
The catalog number carries more engineering information than the product name. Voltage class, current rating, enclosure, keypad type, emission class and communication slot are all encoded in twelve characters, and decoding them is faster than opening three documents to answer a quotation.
Overload behaviour is a published curve, not a guess. The motor overload parameter defaults to the drive rated current and the drive trips at 150 percent for sixty seconds, which is what a pump needs on a cold start and what a fan with a high inertia load will test every morning.
The parameter set is deliberately small for fan and pump duty. Current limit, motor overload, minimum and maximum frequency and the analog input scaling cover most of a commissioning, and the rest is the application logic that the plant decides rather than the drive.
Frame size is the physical consequence of rating. It fixes the terminal bolt size, the torque, the mounting clearances and the enclosure options allowed, so a change of frame is a change of panel layout rather than a substitution of one part number for another.
The 240 volt and the 480 volt families differ in more than insulation. The same 2.2 kW rating lands on 12 amps at 240 volts and 6 amps at 480 volts, which changes the cable, the contactor and the filter, and comparing two catalog numbers by kW alone hides that.
A drive is a harmonic and high frequency noise source, and the compliance tables exist because of that. Terminating the motor cable shield at both ends, keeping the cable short and installing the specified filter are the three measures that make a panel acceptable in a plant with other electronics.
Enclosure code is the difference between a drive that can sit on a wall and one that has to sit in a cabinet. The open type and the flange mount are both IP20, and the NEMA 1 variant of the small frame is a field conversion rather than a separate product on the C frame.
Keypad type is part of the ordering code because the fixed keypad is not removable on some frames. A project that plans to mount the keypad remotely has to decide that at specification stage, and the keypad and communication appendix is where that decision is documented.
Spares strategy follows the frame and the filter, not the kW. A site with several 2.2 kW units on one frame shares the same filter and the same option kits, while a single 200 kW unit needs its own filter and its own lifting plan.
The filter line in the compliance tables is the part most often forgotten in a quotation. A drive sold unfiltered still has to meet the emission class the site requires, and the external filter plus its motor cable limit is the difference between passing an EMC inspection and reworking a run.
RS485 is the built in network option on this family, and the communication slot code is what shows whether it is present. Two DSI ports exist on the larger frames, and using one blocks the other, which matters when a keypad and a network adapter are both wanted.
A fan and pump drive is specified by shaft power, not by nameplate amps alone. The rating table gives both, and the pair has to be read together: the amp figure sizes the cable and the protection, the kW figure decides whether the fan curve at full speed is inside the drive.
Confirm the enclosure rating from the nameplate before installation, then apply the standard 240 volt filter and cable rules for this rating.
Other catalog numbers and accessories for the same range are collected in the Allen-Bradley PowerFlex drives and motors category.