Product Details:
Payment & Shipping Terms:
|
This page documents catalog number 22B-A2P3C104, a PowerFlex 40 drive: 240 V AC single-phase, 2.3 A, 0.4 kW (0.5 HP), enclosure C, frame B. The decode and every figure below come from the drive family's published selection and installation tables; the option positions the documentation does not resolve are named as unresolved rather than guessed.
| Field | Value |
| Catalog number | 22B-A2P3C104 |
| Family (characters 1-3) | 22B - PowerFlex 40 adjustable frequency AC drive |
| Voltage class (character 5) | A - 240 V AC single-phase |
| Input band as published | 200-240 V AC |
| Output as published | 0-230 V three-phase |
| Rating code (characters 6-8) | 2P3 - 2.3 A, 0.4 kW (0.5 HP) |
| Frame size | B |
| Enclosure (character 9) | C - IP66, NEMA/UL Type 4X |
| Emission class (character 11) | 0 - no integral filter (unfiltered drive) |
| Drive type (character 12) | 4 - the family notes that this position indicates drive type and that all PowerFlex 40 drives carry RS485 |
The 240 V single-phase class is the answer to a machine that has to run without a three-phase supply. Four codes cover 2.3 A to 12 A and 0.4 to 2.2 kW, and the output is a three-phase waveform the motor cannot distinguish from a three-phase feed.
Single-phase input changes the wiring, not the motor. The rectifier draws from two conductors, so the supply cable and the upstream protection are sized single-phase while the motor cable stays a three-phase run. That asymmetry is where most installation mistakes on this class begin.
The enclosure character of 22B-A2P3C104 reads C, which the family defines as IP66 and NEMA/UL Type 4X: a sealed, panel-mount drive that can stand on the machine rather than inside a cabinet, removing the enclosure from the project scope.
There is a published limit that decides whether this variant can be ordered at all. The family states that IP66 and NEMA/UL Type 4X drives are not available in frame C ratings, so a rating sitting on frame C has no IP66 version and a specification asking for both has asked for something the family does not build.
On frame B of 22B-A2P3C104 the published power terminal block accepts 5.3 mm2 (10 AWG) maximum and 1.3 mm2 (16 AWG) minimum at 1.7-2.2 N-m (16-19 lb-in), and the I/O terminal block common to frames B and C accepts 1.3 mm2 (16 AWG) maximum and 0.2 mm2 (24 AWG) minimum at 0.5-0.8 N-m. The frame measures 100 x 180 x 136 mm and ships at 2.2 kg.
The emission character reads 0. At 1 the string describes a drive with the integral S-type EMC filter the family lists for this rating; at 0 it describes an unfiltered drive, and the EMC obligation moves to the installation. The manual also gives the cable lengths the two filter families allow: S type for at least 10 m in a Class A environment and 1 m in Class B, L type for at least 100 m in Class A and 5 m in Class B. A filter is not inferable from the power rating, only from this character, which is why 22B-A2P3C104 is read at that position before anything else.
The enclosure does not upgrade the drive; it carries the rating of the enclosure around it, and 22B-A2P3C104 is no exception. The manual states that the drive meets IP40, IP54 and IP65 for NEMA 1, 12, 4 and 4X only when installed inside an enclosure of like rating, which is the sentence that decides whether an open drive is acceptable in a given room.
Dynamic braking on 22B-A2P3C104 is a resistor selection rather than a drive setting: the manual lists 48 ohm, AK-R2-091P500 for this kW rating, and the resistors are rated for 5 percent duty cycle. The resistance changes with the rating rather than staying fixed, so a resistor carried over from a different size does not transfer.
Where the drive needs a line reactor or a DC bus inductor, the manual lists the Bulletin 1321-3R series and the MTE RB series by drive rating, and the larger ratings of the 480 V class are flagged as requiring an external DC bus inductor or AC line reactor rather than being usable bare. For 22B-A2P3C104 the reactor line therefore stays a bill-of-materials question rather than a commissioning note.
The string settles voltage class, output current, enclosure, filter and drive type. It does not settle the motor, the cable, the upstream protection or the duty, and on a drive of this size those four decide whether the installation works. 22B-A2P3C104 is the drive's capability; the installation around it is the engineer's.
Two drives of this family can share a current and a voltage and differ in enclosure or filter, so a spare order that quotes a rounded-off number can produce a unit that runs the motor and does not fit the panel. 22B-A2P3C104 is one of those strings, and quoting it in full is the discipline that prevents that.
In 22B-A2P3C104 the interface position reads 1. The 22B family carries an interface module code in that position, and every PowerFlex 40 drive is stated to include RS485 communication regardless of it, so the RS485 link is a property of the drive rather than of the option. On this page the 1 is not translated into a module type, because the selection table resolves it by rating and the position is not self-describing.
Commissioning a drive of this class starts with the two numbers the string does not carry: the motor nameplate current, which the drive must be limited to, and the acceleration the machine actually needs. On 22B-A2P3C104 the current limit is set from the motor nameplate rather than from the rating row, because a drive this small is usually protecting a motor rather than controlling a process.
No lifecycle statement and no price is implied. The rating rows, the voltage bands, the enclosure definitions, the terminal and frame data, the filter cable limits, the braking resistor selections and the reactor notes behind 22B-A2P3C104 are quoted from the drive family's published selection and installation tables.
Each code in this class is a separate published row rather than a step on a frame ladder: current, frame and braking resistor all move together, and only the enclosure and interface characters are free. The rows below carry the current and the resistor the manual lists for this class, which is what a spare order has to match.
| Rating code | kW | HP | Output A | Frame | Brake resistor |
|---|---|---|---|---|---|
| 22B-A2P3 | 0.4 | 0.5 | 2.3 | B | 48 ohm, AK-R2-091P500 |
| 22B-A5P0 | 0.75 | 1.0 | 5.0 | B | 48 ohm, AK-R2-091P500 |
| 22B-A8P0 | 1.5 | 2.0 | 8.0 | B | 48 ohm, AK-R2-091P500 |
| 22B-A012 | 2.2 | 3.0 | 12.0 | C | 32 ohm, AK-R2-047P500 |
This code is row 1 of 4 in the class: 0.4 kW (0.5 HP) at 2.3 A continuous output on frame B, with a 48 ohm, AK-R2-091P500 braking resistor. The enclosure character on this number reads IP66, NEMA/UL Type 4X, which is one of the forms the family publishes for this rating: it changes the housing and the drawing, not the current, the frame or the resistor. The next code, 22B-A5P0, is 5.0 A on frame B. It is the smallest rating the class publishes.
Crossing from frame B to frame C is the one step that changes the cabinet: 22B-A8P0 sits at 100 x 180 x 136 mm and 2.2 kg, 22B-A012 at 130 x 260 x 180 mm and 4.3 kg, and the power terminal grows from 5.3 mm2 (10 AWG) maximum at 1.7-2.2 N-m (16-19 lb-in) to 8.4 mm2 (8 AWG) maximum at 2.9-3.7 N-m (26-33 lb-in). A panel drawing that was right for the smaller code is wrong for the larger one by that much, before the motor cable is even considered.
This is a single-phase class whose output is three-phase from 0 to 230 V: the drive converts phase as well as frequency. That is why a 120 V or 240 V single-phase feed can run an ordinary three-phase motor, and it is also why the current on this ladder is an output current - the input current on a single-phase feed is higher for the same kilowatts, and the feeder is sized from the installation tables rather than from this column.
The ladder does not carry the branch fuse or the motor protector for 22B-A2P3C104, and that is not an omission of this page: the family resolves both per rating in its installation tables. A bill of materials assembled from the selection ladder alone leaves two lines for the panel builder, and both are protection decisions rather than accessories.
Twelve of the 112 22B records this shop lists, chosen by code proximity so that the nearest options are one click away. This page is 22B-A2P3C104.
Group index: AB Drives & Motors. 22B-A2P3C104 is filed under that heading in the site's own product tree.
Sources. Rockwell publishes the PowerFlex 40 user manual as 22B-UM001, and the technical data for the PowerFlex 4 and 40 ranges as 22-TD001. The ratings, terminal designations and ordering characters quoted on this page for 22B-A2P3C104 follow those two publications.