Product Details:
Payment & Shipping Terms:
|
The 1769-OV16 (also written 1769OV16) is the sinking sixteen-point 24V DC output: the points switch the DC common side, so the field device's positive terminal sits permanently on +24V and the PLC completes the circuit to return.
Functionally it mirrors the 1769-OB16 — same 0.5 A per point at 60 °C, same 0.1 ms switching, same 1.0 mA leakage, same 2 A surge. The two are not interchangeable at the terminals: a sourcing module on a sinking-wired panel leaves every load permanently energised, and that is the single most expensive mistake in this family.
| 1769-IA16 | Compact 16-point 120V AC input module | IN STOCK |
| 1769-IQ16 | Compact 16-point 24V DC sink/source input module | IN STOCK |
| 1769-IQ32 | Compact 32-point 24V DC sink/source input module | IN STOCK |
| 1769-OA16 | Compact 16-point 120/240V AC output module | IN STOCK |
| 1769-OB16 | Compact 16-point 24V DC output module | IN STOCK |
| 1769-OB32 | Compact 32-point 24V DC output module | IN STOCK |
| 1769-OW16 | Compact 16-point relay output module | IN STOCK |
| 1769-IF4 | Compact 4-channel analog input module | IN STOCK |
| 1769-IF8 | Compact 8-channel analog input module | IN STOCK |
| 1769-IF16C | Compact 16-channel current input module | IN STOCK |
| 1769-OF4 | Compact 4-channel analog output module | IN STOCK |
| 1769-OF8V | Compact 8-channel voltage output module | IN STOCK |
| 1769-OF8C | Compact 8-channel current output module | IN STOCK |
| 1769-ARM | Compact address reserve module | IN STOCK |
Application |
Compact I/O, 1769 bus |
Cat Num |
1769-OV16 |
Brand Name |
Rockwell |
Outputs |
16 (16 points per group, one DC common) |
Voltage category |
24V DC sink |
Operating voltage range |
20.4…26.4V DC |
Output delay, on / off |
0.1 ms / 1.0 ms |
Current draw @ 5.1V |
200 mA |
Heat dissipation, max |
2.06 W |
Off-state leakage, max |
1.0 mA @ 26.4V DC |
On-state current, min |
1.0 mA |
On-state voltage drop, max |
1.0V DC @ 1 A |
Current per point |
0.5 A @ 60 °C; 1.0 A @ 30 °C |
Current per module |
4.0 A @ 60 °C; 8.0 A @ 30 °C |
Surge current |
2.0 A for 10 ms, repeatable every 2 s |
Isolation |
1200V AC 1 s or 1697V DC 1 s, point to bus; 75V DC working voltage |
Slot width / weight |
1 slot / 280 g |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1769-TD006 (module specifications) and 1769-SG001 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
What is the difference between 1769-OV16 and 1769-OB16?
1769-OV16 switches the DC common (sinking); 1769-OB16 switches +VDC (sourcing). Ratings are otherwise the same, but the field wiring is mirrored and the two cannot be swapped without rewiring.
How much current can 1769-OV16 switch?
0.5 A per point and 4.0 A per module at 60 °C; 1.0 A and 8.0 A at 30 °C.
What does 1769-OV16 draw from the backplane?
200 mA at 5.1V with 2.06 W maximum heat dissipation, one slot, 280 g, eight-module distance rating.
What happens if a sourcing module is used on a sinking panel?
The loads are held energised because the module switches the wrong side of the circuit. 1769-OV16 is the correct part for a sinking field wiring convention.
What field voltage does 1769-OV16 require?
20.4…26.4V DC, with 0.1 ms on and 1.0 ms off switching and 1.0V DC maximum drop at 1 A.
Does 1769-OV16 need a diode on inductive loads?
Yes — a 1N4004 reverse-wired across each 24V DC coil, exactly as for the sourcing module. The diode is fitted across the load.