Product Details:
Payment & Shipping Terms:
|
The 1769-CJC is the cold junction compensation accessory for the 1769 thermocouple input modules — the part that gives the module a known reference temperature at the terminal block, without which a thermocouple reading is only a voltage.
It is a small accessory with a large effect on accuracy: a thermocouple measures the difference between the hot junction in the process and the junction where the wires land, and the CJC is what tells the module the temperature of that second junction.
| 1769-IA16 | Compact 16-point 120V AC input module | IN STOCK |
| 1769-IQ16 | Compact 16-point 24V DC sink/source input module | IN STOCK |
| 1769-IQ32 | Compact 32-point 24V DC sink/source input module | IN STOCK |
| 1769-OA16 | Compact 16-point 120/240V AC output module | IN STOCK |
| 1769-OB16 | Compact 16-point 24V DC output module | IN STOCK |
| 1769-OB32 | Compact 32-point 24V DC output module | IN STOCK |
| 1769-OW16 | Compact 16-point relay output module | IN STOCK |
| 1769-IF4 | Compact 4-channel analog input module | IN STOCK |
| 1769-IF8 | Compact 8-channel analog input module | IN STOCK |
| 1769-IF16C | Compact 16-channel current input module | IN STOCK |
| 1769-OF4 | Compact 4-channel analog output module | IN STOCK |
| 1769-OF8V | Compact 8-channel voltage output module | IN STOCK |
| 1769-OF8C | Compact 8-channel current output module | IN STOCK |
| 1769-ARM | Compact address reserve module | IN STOCK |
Application |
Cold junction compensation for 1769 thermocouple input modules |
Cat Num |
1769-CJC |
Brand Name |
Rockwell |
Type |
Accessory, thermocouple reference junction |
Used with |
1769 thermocouple modules in L2 controller thermocouple mode |
Ordering |
By catalog number; no separate technical data table published |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1769-TD006 (module specifications) and 1769-SG001 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
What does the 1769-CJC do?
It provides the cold junction reference temperature that a 1769 thermocouple input module needs to convert a millivolt signal into a correct temperature reading.
Why is cold junction compensation necessary?
A thermocouple measures the difference between the process junction and the terminal junction; without knowing the terminal temperature the reading carries an ambient offset.
How many 1769-CJC parts are needed?
One per thermocouple input module, since the reference serves the module's channels.
Is the 1769-CJC used with RTD modules?
No. RTD modules measure resistance and need no cold junction compensation.
Does Rockwell publish a data table for the 1769-CJC?
No. It is listed as a Compact I/O accessory by catalog number, without separate dimensional or electrical specifications.
Where should the terminal block sit?
Away from heat sources such as drives and power supplies, so the reference temperature it measures is representative.
Does cold junction compensation affect all channels on the module?
Yes. One reference at the terminal block is applied across the module's thermocouple channels.
Is the CJC required for a millivolt input?
No. A plain voltage input is not a thermocouple measurement and does not use the compensation.
1769-CJC is listed in the 1769 Compact I/O range. The family is a row-based I/O system: modules lock together with a tongue-and-groove joint, the bus is passed module to module by a moveable connector, each I/O module carries its own removable terminal block behind a front door, and the row is closed with an end cap.
| Attribute | Value |
| Catalog number | 1769-CJC |
| Family | 1769 Compact I/O |
| Mounting | Row assembly with end cap, bus carried module to module |
| Field wiring | Built-in removable terminal block per I/O module |
| Row budget | Backplane current quoted at 5.1V, plus 24V where the module uses it |
| Distance rule | Power supply distance rating, typically 8 slots, 6 for 1769-OB32, 5 for 1769-AENTR |
| Coated variant | A K suffix marks conformal coating |
Because the terminal block belongs to the module rather than to a separate base, the spare-part logic in this family is the module and not the base: a replacement module arrives with its own terminations, and the wiring has to be moved across unless the block is removed and refitted. That is a maintenance procedure, not a parts problem, and it is the reason a 1769 row is usually replaced module by module during a shutdown rather than block by block.
Every 1769 I/O module carries a power supply distance rating, and that rating is how many slot positions the module may sit from the power supply. Most digital and analog modules are rated 8, the 1769-OB32 is rated 6 and the 1769-AENTR adapter is rated 5, so a long row of 32-point outputs can be electrically legal and still outside the distance rating of the supply that feeds it.
Backplane current in this family is quoted at 5.1V, not 5V, and the difference matters when a row is budgeted: 1769-OB32 draws 300 mA at 5.1V, 1769-OA16 draws 225 mA, 1769-IQ32 draws 170 mA, and the analog RTD and thermocouple modules draw 100 mA at 5.1V plus 45 mA at 24V. A supply sized on the 5V number alone is close enough to be tempting and wrong enough to brown out the last module in the row.
Analog and temperature modules in this family carry a second rail: the 1769-IR6 and 1769-IT6 take 100 mA at 5.1V and 45 mA at 24V, so a row that mixes them with digital I/O has to be checked on both rails. The 24V figure is small in absolute terms and still disqualifying when the 24V budget was calculated from digital modules that draw nothing from it.
The K suffix in this range means conformal coating, and it is applied across the whole family rather than to a single module: 1769-IA8K, 1769-IQ16K, 1769-OB16K and 1769-PA2K are the coated equivalents of their plain counterparts. In a corrosive or condensing environment the coated variant is the specification, and the plain part is not made acceptable by adding a cabinet heater.
Confirm the part against the module it serves in the 1769 selection guide before quoting it, confirm the row current on both the 5.1V and 24V rails, and confirm that the distance rating of the last module in the row still falls inside the rating of the supply that feeds it.
The Allen-Bradley CompactLogix 1769 controllers category groups the other catalog numbers, options and spare parts in the same range.