This page documents the 22F-B4P2N103, a PowerFlex 4M (bulletin 22F) drive in the 240 V three-phase class: 0.75 kW (1.0 HP), 4.2 A continuous output, frame A, IP20 panel mount, without integral EMC filter. The rating, the frame, the terminal sizes, the protection rows and the cable allowances are quoted from the PowerFlex 4M user manual 22F-UM001.
| Field | Value |
| Catalog number | 22F-B4P2N103 |
| Family | 22F - PowerFlex 4M, adjustable frequency AC drive, IP20 panel mount only |
| Voltage code (character 5) | B - 240 V three-phase |
| Rating code (characters 6-8) | 4P2 - 0.75 kW (1.0 HP), 4.2 A continuous |
| Frame | A |
| Enclosure (character 9) | N - IP20, the only enclosure form this family publishes |
| HIM position (character 10) | 1 |
| Emission class (character 11) | 0 - without integral EMC filter |
| Type (character 12) | 3 - carried, resolved in the option appendix rather than here |
| Positions 13-14 | not used on this string |
| Attribute | Value |
| Output current | 4.2 A continuous |
| Motor rating | 0.75 kW (1.0 HP) |
| Input window | 180-265 V |
| Frame | A |
| Terminal block | 3.3 mm2 (12 AWG) maximum, 0.8 mm2 (18 AWG) minimum, 1.4-1.6 N.m (12-14 lb-in) |
| Input kVA | 2.1 |
| Input current | 4.9 A |
| Fuse, 40 C NEC | 10 A |
| 140M / 140MT controller | 140M-C2E-B63 or 140MT-C3E-B63 |
| Contactor | 100-C09 or 100-E09 |
| Minimum enclosure volume | 1,655 in3 |
Frame A sets the terminal block to 3.3 mm2 (12 AWG) maximum and 0.8 mm2 (18 AWG) minimum at 1.4-1.6 N.m (12-14 lb-in). Those are the sizes the block accepts, not a recommendation for the motor lead, and the minimum is what decides whether a small motor cable can be landed directly or has to go through a junction.
The 4M does not provide branch short-circuit protection. It has to be installed with input fuses or an input circuit breaker, and national and local codes can add requirements on top of that. The manual states the point twice and adds an attention note about using only the recommended line fuses or breakers, because an improvised device voids the basis on which the drive was tested. This entry is for 22F-B4P2N103.
| Protection item | Published value |
| Fuse | 10 A at 40 C (104 F), NEC basis |
| Self-protected combination controller | 140M-C2E-B63 or 140MT-C3E-B63 |
| MCS contactor | 100-C09 or 100-E09 |
| Minimum enclosure volume | 1,655 cubic inches |
| DC fuse position | 1000GH-016 where this row publishes it |
The fuse class is part of the requirement, not a preference: BS88 parts 1 and 2 or EN60269-1 type gG for IEC installations, Class CC, T or J for UL. A fuse of the right amperage in the wrong class does not satisfy the table it came from.
Read as a whole row rather than as four separate lookups, the numbers for this string are 4.2 A output, 0.75 kW (1.0 HP) at 180-265 V, a 10 A fuse, a 140M-C2E-B63 or 140MT-C3E-B63 controller and a 100-C09 or 100-E09 contactor in at least 1,655 cubic inches. Those four move together: a panel built to a larger fuse than the row states is a panel whose protection no longer matches the drive it was tested with.
Character 11 reads 0, so this drive ships without integral EMC filter. The character does not change the rating, the frame or the terminal block; it changes the EMC environment the drive may be installed in and the motor cable length the manual permits.
Because no filter is inside the drive, an installation in a regulated environment needs an external unit in the panel: an S-type filter for a short lead or an L-type filter for a long one, with the allowances published for each. The 4.2 A rating and frame A are the same as the filtered string of the same rating; what changes is the cable length that can be certified, so a site survey that measures the motor lead comes before the order, not after it.
| Filter route | Second environment | First environment, unrestricted distribution |
| Integral filter, 240 V drive | 5 m | 1 m |
| Integral filter, 480 V drive | 10 m | see the same table in 22F-UM001 |
| External S-type filter | 5 m | 1 m |
| External L-type filter | 100 m | 25 m |
An unfiltered drive on a long motor lead is a drive that fails an emissions check later, and the correction at that point is an external filter plus a retest rather than a catalog change. That is the practical reason a filtered code is ordered even where no regulation is quoted at the quotation stage. 22F-B4P2N103 is the number described on this page.
Output current is limited in software rather than by the frame. The current-limit parameter defaults to 1.5 times the drive rated amps and can be raised to 1.8 times, and the output-current monitor reads up to twice the rated amps. A drive one frame larger than the motor is therefore made safe for that motor by a parameter setting, and a machine that needs a slower ramp needs a different parameter rather thans for 22F-B4P2N103.
Reorder risk on the emission character. Two drives with the same rating and different character 11 are different products when the cable run is long. A spare ordered by rating alone can arrive unfiltered into an installation that was commissioned with a filter, and the mismatch shows up as an emission problem rather than as a wrong part number.
The two things a 4m does not contain. The 4M carries no branch short-circuit protection and no integral EMC filter on the unfiltered codes. Both have to be supplied around it: fuses or a circuit breaker upstream, and either the integral filter option or an external filter where the installation is regulated. A panel drawn around a bare 4M is a panel whose protection and emission compliance live in other line items.
Single-phase input, three-phase output. A 240 V single-phase 4M produces three-phase output from a single-phase supply, which is why small conveyors and fans in light-duty panels can use it at all. The motor is still a three-phase motor, and the input and output phase counts are two separate questions on this family.
Filter class decides the motor lead. The emission character does not change the rating, the frame or the terminals; it changes the environment the drive may be installed in and the motor cable length the manual allows. An integral 240 V filter is good for 5 m in the second environment, an integral 480 V filter for 10 m, an external S-type filter for 5 m, and an external L-type filter for 100 m outside the unrestricted first environment.
Frame letters and the wire that fits. Frames A, B and C set both the terminal block and the panel footprint: 12 AWG maximum on frame A, 8 AWG on frame B, 6 AWG on frame C. The minimum sizes matter as much as the maximum, because a small motor cable below the block minimum has to be landed through a junction rather than directly.
Panel thermal and mounting. Estimated watts loss is published per rating at rated load, rated speed and rated PWM, and it is a drive-only figure used in the panel thermal calculation. Panel mounting is the only form this family publishes, with a 1.9 mm minimum panel thickness and M4 screws as for 22F-B4P2N103.
The 4M is the small-machine drive in this family, and the tell is in the protection table: it is the drive that does not carry branch short-circuit protection internally, so the panel around it has to supply it.