This page documents catalog number 22F-B017N103, a PowerFlex 4M (bulletin 22F) drive on the 240 V three-phase class: 3.7 kW (5.0 HP), 17.5 A continuous output, frame B, IP20 panel mount, the only enclosure form this family publishes, without integral EMC filter. The rating, frame, terminal sizes and protection figures are taken from the published PowerFlex 4M user manual rather than from a nameplate.
| Field | Value |
| Catalog number | 22F-B017N103 |
| Family | 22F - PowerFlex 4M adjustable frequency AC drive |
| Voltage code (character 5) | B - 240 V three-phase input |
| Rating code (characters 6-8) | 017 - 3.7 kW (5.0 HP), 17.5 A |
| Frame | B |
| Enclosure (character 9) | N - IP20 panel mount, the only enclosure form this family publishes |
| HIM position (character 10) | 1 |
| Emission class (character 11) | 0 - without integral EMC filter |
| Type (character 12) | 3 - carried, not translated on this page |
| Optional positions 13-14 |
The published row for this code gives 17.5 A continuous output at 3.7 kW (5.0 HP) across a 180-265 V input window, in frame B. The manual also lists 8.8 kVA and 21.1 A on the input side for this row.
A 240 V single-phase drive produces three-phase output; the phase count on the input and the phase count on the output are two different questions on this family, and a drive bought for a single-phase panel still needs a three-phase motor.
Frame B sets the terminal block: maximum 8.4 mm2 (8 AWG), minimum 0.8 mm2 (18 AWG), at 1.6-1.9 N.m (14-17 lb-in). Those are the sizes the block accepts, not a recommendation, and the minimum is the one that decides whether a small motor cable can be landed directly or needs a junction.
The 4M does not provide branch short-circuit protection. It has to be installed with either input fuses or an input circuit breaker, and national and local codes can add requirements on top of that. The manual states the point twice and adds an attention note about using only the recommended line fuses or breakers, because an improvised device voids the basis on which the drive was tested.
For this rating the manual gives a 35 A fuse at 40 degrees C with NEC guidance, with 140M-D8E-C25 or 140MT-D9E-C25 as the self-protected combination controller and 100-C23 or 100-E26 as the MCS contactor, in a minimum enclosure volume of 1,655 cubic inches. The DC fuse positions are published too: 1000GH-050 for BR+/DC+ and DC-.
The fuses are constrained by class as well as size: BS88 parts 1 and 2 or EN60269-1 type gG for IEC installations, and Class CC, T or J for UL. The manual adds that Bulletin 140M/140MT controllers may sit upstream of the drive without fuses, which is the route that saves panel width when a self-protected controller is already in the design.
Character 11 reads 0, so this drive ships without integral EMC filter. The emission character does not change the rating, the frame or the terminal block; it changes the EMC environment the drive can be installed in and the motor cable length the manual permits.
The published allowances separate the two filter routes: an integral filter on a 240 V drive is good for 5 m in the second environment and 1 m in the first environment with unrestricted distribution, an integral 480 V filter for 10 m in the second environment, an external S-type filter for 5 m and 1 m on the same split, and an external L-type filter for 100 m in the first two cases and 25 m in the unrestricted first environment.
Those numbers are the reason a filtered drive is ordered even when the panel is not in a regulated environment: an unfiltered drive with a long motor lead is a drive that fails an emissions test later, and the fix at that point is an external filter and a re-test rather than a catalogue change.
The estimated watts loss for this rating is published in the loss table of the manual; it is the figure a panel thermal calculation uses and it is a drive-only figure, not the motor or the enclosure.
Output current is limited in software rather than by the frame: the current-limit parameter defaults to 1.5 times the drive rated amps and can be raised to 1.8 times, and the output-current monitor reads up to twice the rated amps. A 4M therefore protects a motor that is smaller than its rating by a parameter setting rather than by a different catalog number.
The string does not settle the HIM, the communications option or the braking resistor. Type character 3 is carried rather than translated here, and the option appendix resolves the HIM and filter part numbers per code, which is the only safe route to a spare.
A 4M is often bought as a spare for a machine that already runs one, and the character that is easy to get wrong on a reorder is the emission character: a filtered and an unfiltered drive have the same rating but not the same cable allowance.
No lifecycle statement and no price is implied. The rating, frame, terminal, protection and cable-length figures are quoted from the PowerFlex 4M user manual, publication 22F-UM001.
Parameter access follows the drive rather than the panel: over Modbus the register address equals the parameter number, so decimal 1 addresses d001 [Output Freq] and decimal 109 addresses P109 [Accel Time 1]. A controls engineer commissioning from a PLC therefore needs the parameter list, not the catalog string, and the string is the part that must be right before that work starts.
This record is placed on the six-record 22F PowerFlex 4M ladder carried on this site. The first table is the rating each record prints or declines to print; the second is the protection and enclosure that follows from it. Both quote only what the individual pages state, and a record whose page refers a field to 22F-UM001 is marked as not printed rather than filled in from a neighbouring rating.
| Catalog number | Voltage class | Output current | Rated power | Frame | Input window | Input kVA / current |
| 22F-A2P5N103 | A - 240 V single-phase | 2.5 A | 0.4 kW (0.5 HP) | A | 180-265 V | 1.6 kVA / 6.5 A |
| 22F-A4P2N103 | A - 240 V single-phase | 4.2 A | not printed - referred to 22F-UM001 | not printed | 180-265 V (class level) | not printed |
| 22F-A4P2N113 | A - 240 V single-phase | 4.2 A | not printed - referred to 22F-UM001 | not printed | 180-265 V (class level) | not printed |
| 22F-B017N103 | B - 240 V three-phase | 17.5 A | 3.7 kW (5.0 HP) | B | 180-265 V | 8.8 kVA / 21.1 A |
| 22F-D018N104 | D - 480 V three-phase | 18.0 A | 7.5 kW (10.0 HP) | C | 340-528 V | 16.3 kVA / 19.5 A |
| 22F-D024N104 | D - 480 V three-phase | 24.0 A | 11.0 kW (15.0 HP) | C | 340-528 V | 21.7 kVA / 26.1 A |
Protection and enclosure that follow. The line fuse is a function of the input current, and the enclosure volume is a function of the frame.
| Catalog number | Line fuse at 40 C | 140M / 140MT upstream | Contactor | Min enclosure volume |
| 22F-A2P5N103 | 10 A | 140M-C2E-C10 / 140MT-C3E-C10 | 100-C09 / 100-E09 | 1,655 in3 |
| 22F-A4P2N103 | not printed - referred to 22F-UM001 | not printed | not printed | not printed |
| 22F-A4P2N113 | not printed - referred to 22F-UM001 | not printed | not printed | not printed |
| 22F-B017N103 | 35 A | 140M-D8E-C25 / 140MT-D9E-C25 | 100-C23 / 100-E26 | 1,655 in3 |
| 22F-D018N104 | 30 A | 140M-F8E-C25 | 100-C23 / 100-E26 | 3,441 in3 |
| 22F-D024N104 | 40 A | 140M-F8E-C32 | 100-C30 / 100-E30 | 3,441 in3 |
Where this record sits: the only three-phase 240 V record here, 17.5 A in frame B, which is the frame that shares its 1,655 cubic inch enclosure volume with frame A while frame C doubles it.
The frame, not the power, sets the mechanical facts. Frames A and B both print a 1,655 cubic inch minimum enclosure volume, and frame C doubles it to 3,441 cubic inches - yet the two frame C records differ by 3.5 kW and stay on the same volume. The terminal range moves the other way at the top: frames A and B accept down to 0.8 mm2 (18 AWG), while frame C bottoms out at 3.3 mm2 (12 AWG) and 2.7-3.2 N.m, so a small motor cable cannot be landed directly on the largest drive in this group.
What these pages do not carry: no enclosure dimensions, only the minimum volume in cubic inches, so the panel layout has to come from the manual; no drive weight; no efficiency, loss or thermal figure; no overload percentage for the thermal model; and on the two 4.2 A records no kW, HP, frame, kVA, input current, fuse, contactor or enclosure volume at all, because those pages deliberately refer the rating row to 22F-UM001 rather than reproduce it.
This is the only 240 V three-phase record in the batch, and it prints the only 35 A line fuse: 21.1 A of input current against 17.5 A of output on a 240 V three-phase feed. Note that the page text says a 240 V single-phase drive produces three-phase output, which is the sentence this record should not carry - a B code is three-phase on the input as well.
Source: the decode tables and body text printed on the six 22F records on this site, which cite 22F-UM001 for the rating rows, the fuse and enclosure volumes; the output currents, kW and HP figures, input windows, kVA and input currents, terminal ranges, torques, fuse ratings, 140M/140MT and contactor part numbers, enclosure volumes and DC fuse numbers are quoted from the records that print them, and fields a record refers to the manual are shown as not printed.
This page links twelve of the 34 22F records on this site; the closest rating codes come first. This page is 22F-B017N103.
For the surrounding range, open the AB Drives & Motors catalogue index — 22F-B017N103 is listed there beside the rest of the drive and motor group.