This page documents catalog number 22B-E012H204, a PowerFlex 40 drive: 600 V AC three-phase, 12.2 A, 7.5 kW (10 HP), enclosure H, frame C. The decode and every figure below come from the drive family's published selection and installation tables; the option positions the documentation does not resolve are named as unresolved rather than guessed.
| Field | Value |
| Catalog number | 22B-E012H204 |
| Family (characters 1-3) | 22B - PowerFlex 40 adjustable frequency AC drive |
| Voltage class (character 5) | E - 600 V AC three-phase |
| Input band as published | 500-600 V AC (414-660 V window) |
| Output as published | 0-575 V three-phase |
| Rating code (characters 6-8) | 012 - 12.2 A, 7.5 kW (10 HP) |
| Frame size | C |
| Enclosure (character 9) | H - IP20 replacement plate drive |
| Emission class (character 11) | 0 - no integral filter (unfiltered drive) |
| Drive type (character 12) | 4 - the family notes that this position indicates drive type and that all PowerFlex 40 drives carry RS485 |
The 600 V three-phase class covers installations where 600 V is the distribution rather than a transformed 480 V. Seven codes span 1.7 A to 19 A and 0.75 to 11 kW, with an input window of 414 to 660 V and an output range of 0 to 575 V.
The currents in this class are lower than the 480 V class at the same power, which is arithmetic rather than design: the same kilowatts at a higher voltage need fewer amps. A buyer comparing the two tables by current alone will misread the 600 V drives as smaller machines.
The enclosure character reads H, which the drive's selection table gives as the IP20 replacement plate drive variant, a form intended for a drive that replaces an existing unit on a mounting plate rather than for a new panel build.
A replacement plate variant is a fit-to-existing-hardware decision before it is an electrical one. The mounting interface and the space it occupies are properties of this variant, so a substitution toward or away from it changes the mechanical installation even when the rating is identical.
On frame C the published power terminal block accepts 8.4 mm2 (8 AWG) maximum and 1.3 mm2 (16 AWG) minimum at 2.9-3.7 N-m (26-33 lb-in), and the I/O terminal block common to frames B and C accepts 1.3 mm2 (16 AWG) maximum and 0.2 mm2 (24 AWG) minimum at 0.5-0.8 N-m. The frame measures 130 x 260 x 180 mm and ships at 4.3 kg.
The emission character reads 0. At 1 the string describes a drive with the integral S-type EMC filter the family lists for this rating; at 0 it describes an unfiltered drive, and the EMC obligation moves to the installation. The manual also gives the cable lengths the two filter families allow: S type for at least 10 m in a Class A environment and 1 m in Class B, L type for at least 100 m in Class A and 5 m in Class B. A filter is not inferable from the power rating, only from this character, which is why 22B-E012H204 is read at that position before anything else.
The enclosure does not upgrade the drive; it carries the rating of the enclosure around it, and 22B-E012H204 is no exception. The manual states that the drive meets IP40, IP54 and IP65 for NEMA 1, 12, 4 and 4X only when installed inside an enclosure of like rating, which is the sentence that decides whether an open drive is acceptable in a given room.
Dynamic braking on this rating is a resistor selection rather than a drive setting: the manual lists 51 ohm, AK-R2-120P1K2 for this kW rating, and the resistors are rated for 5 percent duty cycle. The resistance changes with the rating rather than staying fixed, so a resistor carried over from a different size does not transfer.
Where the drive needs a line reactor or a DC bus inductor, the manual lists the Bulletin 1321-3R series and the MTE RB series by drive rating, and the larger ratings of the 480 V class are flagged as requiring an external DC bus inductor or AC line reactor rather than being usable bare. For 22B-E012H204 the reactor line therefore stays a bill-of-materials question rather than a commissioning note.
The string settles voltage class, output current, enclosure, filter and drive type. It does not settle the motor, the cable, the upstream protection or the duty, and on a drive of this size those four decide whether the installation works. 22B-E012H204 is the drive's capability; the installation around it is the engineer's.
Two drives of this family can share a current and a voltage and differ in enclosure or filter, so a spare order that quotes a rounded-off number can produce a unit that runs the motor and does not fit the panel. 22B-E012H204 is one of those strings, and quoting it in full is the discipline that prevents that.
The interface position in this string reads 2. The family carries an interface module code in that position, and every PowerFlex 40 drive is stated to include RS485 communication regardless of it, so the RS485 link is a property of the drive rather than of the option. The 2 value is not translated into a module type on this page, because the selection table resolves it per rating and the position is not self-describing.
Commissioning a drive of this class starts with the two numbers the string does not carry: the motor nameplate current, which the drive must be limited to, and the acceleration the machine actually needs. On 22B-E012H204 the current limit is set from the motor nameplate rather than from the rating row, because a drive this small is usually protecting a motor rather than controlling a process.
No lifecycle statement and no price is implied. The rating rows, the voltage bands, the enclosure definitions, the terminal and frame data, the filter cable limits, the braking resistor selections and the reactor notes behind 22B-E012H204 are quoted from the drive family's published selection and installation tables.
A PowerFlex 40 order is a single rating code, and the code fixes the current, the frame and the braking resistor at once. The ladder below is the published row set for this supply class, with the resistor the manual names for each kilowatt rating; a resistor carried over from a smaller drive is a different part, not an adequate one.
| Rating code | kW | HP | Output A | Frame | Brake resistor |
|---|---|---|---|---|---|
| 22B-E1P7 | 0.75 | 1.0 | 1.7 | B | 120 ohm, AK-R2-360P500 |
| 22B-E3P0 | 1.5 | 2.0 | 3.0 | B | 120 ohm, AK-R2-360P500 |
| 22B-E4P2 | 2.2 | 3.0 | 4.2 | B | 82 ohm, AK-R2-120P1K2 |
| 22B-E6P6 | 4.0 | 5.0 | 6.6 | B | 82 ohm, AK-R2-120P1K2 |
| 22B-E9P9 | 5.5 | 7.5 | 9.9 | C | 51 ohm, AK-R2-120P1K2 |
| 22B-E012 | 7.5 | 10.0 | 12.2 | C | 51 ohm, AK-R2-120P1K2 |
| 22B-E019 | 11.0 | 15.0 | 19.0 | C | 51 ohm, AK-R2-120P1K2 with two resistors in parallel |
This code is row 6 of 7 in the class: 7.5 kW (10.0 HP) at 12.2 A continuous output on frame C, with a 51 ohm, AK-R2-120P1K2 braking resistor. The enclosure character on this number reads IP20 replacement plate drive, which is one of the forms the family publishes for this rating: it changes the housing and the drawing, not the current, the frame or the resistor. The next code, 22B-E019, is 19.0 A on frame C. The code below, 22B-E9P9, stops at 9.9 A, so a motor between the two currents belongs on this rating rather than on the smaller one.
The frame boundary is where the mechanical answer changes rather than the electrical one: 22B-E6P6 is the last code on frame B at 100 x 180 x 136 mm and 2.2 kg, and 22B-E9P9 is the first on frame C at 130 x 260 x 180 mm and 4.3 kg. The power terminal moves from 5.3 mm2 (10 AWG) maximum at 1.7-2.2 N-m (16-19 lb-in) to 8.4 mm2 (8 AWG) maximum at 2.9-3.7 N-m (26-33 lb-in) as well, so the motor cable and not only the rail space has to be re-checked at that step.
Three-phase in and three-phase out means the input and output currents are close but not equal, and neither is a substitute for the other. A panel built on the output amps under-fuses the input; a panel built on the input amps leaves the motor cable outside the protection the drive was listed for.
Two columns a panel schedule wants are deliberately absent: branch-circuit protection and the motor protector. They are resolved per rating in the installation tables rather than in this selection ladder, so a quote built from the ladder alone arrives with the current and the frame settled and the fuse holder still open.
This page links twelve of the 112 22B records on this site; the closest rating codes come first. This page is 22B-E012H204.
For the surrounding range, open the AB Drives & Motors catalogue index — 22B-E012H204 is listed there beside the rest of the drive and motor group. Reach it directly if the suffix on this record still needs confirming against a sibling.
Sources. Rockwell publishes the PowerFlex 40 user manual as 22B-UM001, and the technical data for the PowerFlex 4 and 40 ranges as 22-TD001. The ratings, terminal designations and ordering characters quoted on this page for 22B-E012H204 follow those two publications.