Product Details:
Payment & Shipping Terms:
|
This page documents catalog number 22B-D024F104, a PowerFlex 40 drive: 480 V AC three-phase, 24 A, 11 kW (15 HP), enclosure F, frame C. The decode and every figure below come from the drive family's published selection and installation tables; the option positions the documentation does not resolve are named as unresolved rather than guessed.
| Field | Value |
| Catalog number | 22B-D024F104 |
| Family (characters 1-3) | 22B - PowerFlex 40 adjustable frequency AC drive |
| Voltage class (character 5) | D - 480 V AC three-phase |
| Input band as published | 380-480 V AC (342-528 V window) |
| Output as published | 0-460 V three-phase |
| Rating code (characters 6-8) | 024 - 24 A, 11 kW (15 HP) |
| Frame size | C |
| Enclosure (character 9) | F - IP20 flange mount |
| Emission class (character 11) | 0 - no integral filter (unfiltered drive) |
| Drive type (character 12) | 4 - the family notes that this position indicates drive type and that all PowerFlex 40 drives carry RS485 |
The 480 V three-phase class is the volume class of this family: eight codes from 1.4 A to 24 A and 0.4 to 11 kW, an input window of 342 to 528 V and an output range of 0 to 460 V.
One statement in this class is easy to miss and expensive to forget on 22B-D024F104. The family publishes 35 percent of rated current for single-phase operation of a 480 V drive, so a unit ordered for a three-phase machine and connected to a single-phase feed does not deliver its nameplate current.
The enclosure character of 22B-D024F104 reads F, the IP20 flange-mount variant, where the heatsink passes through the back of the cabinet so the heat leaves the enclosure instead of being circulated inside it.
Flange mounting on 22B-D024F104 is a mechanical commitment rather than an accessory. The cut-out, the heatsink depth and the seal between drive and panel are fixed by the variant, and a cabinet built for an open drive cannot be converted by cutting a hole afterwards without losing the IP20 rating of the assembly.
On frame C of 22B-D024F104 the published power terminal block accepts 8.4 mm2 (8 AWG) maximum and 1.3 mm2 (16 AWG) minimum at 2.9-3.7 N-m (26-33 lb-in), and the I/O terminal block common to frames B and C accepts 1.3 mm2 (16 AWG) maximum and 0.2 mm2 (24 AWG) minimum at 0.5-0.8 N-m. The frame measures 130 x 260 x 180 mm and ships at 4.3 kg.
The emission character reads 0. At 1 the string describes a drive with the integral S-type EMC filter the family lists for this rating; at 0 it describes an unfiltered drive, and the EMC obligation moves to the installation. The manual also gives the cable lengths the two filter families allow: S type for at least 10 m in a Class A environment and 1 m in Class B, L type for at least 100 m in Class A and 5 m in Class B. A filter is not inferable from the power rating, only from this character, which is why 22B-D024F104 is read at that position before anything else.
The enclosure does not upgrade the drive; it carries the rating of the enclosure around it, and 22B-D024F104 is no exception. The manual states that the drive meets IP40, IP54 and IP65 for NEMA 1, 12, 4 and 4X only when installed inside an enclosure of like rating, which is the sentence that decides whether an open drive is acceptable in a given room.
Dynamic braking on 22B-D024F104 is a resistor selection rather than a drive setting: the manual lists 24 ohm, AK-R2-120P1K2 with two resistors in parallel for this kW rating, and the resistors are rated for 5 percent duty cycle. The resistance changes with the rating rather than staying fixed, so a resistor carried over from a different size does not transfer.
Where the drive needs a line reactor or a DC bus inductor, the manual lists the Bulletin 1321-3R series and the MTE RB series by drive rating, and the larger ratings of the 480 V class are flagged as requiring an external DC bus inductor or AC line reactor rather than being usable bare. For 22B-D024F104 the reactor line therefore stays a bill-of-materials question rather than a commissioning note.
The string settles voltage class, output current, enclosure, filter and drive type. It does not settle the motor, the cable, the upstream protection or the duty, and on a drive of this size those four decide whether the installation works. 22B-D024F104 is the drive's capability; the installation around it is the engineer's.
Two drives of this family can share a current and a voltage and differ in enclosure or filter, so a spare order that quotes a rounded-off number can produce a unit that runs the motor and does not fit the panel. 22B-D024F104 is one of those strings, and quoting it in full is the discipline that prevents that.
In 22B-D024F104 the interface position reads 1. The 22B family carries an interface module code in that position, and every PowerFlex 40 drive is stated to include RS485 communication regardless of it, so the RS485 link is a property of the drive rather than of the option. On this page the 1 is not translated into a module type, because the selection table resolves it by rating and the position is not self-describing.
Commissioning a drive of this class starts with the two numbers the string does not carry: the motor nameplate current, which the drive must be limited to, and the acceleration the machine actually needs. On 22B-D024F104 the current limit is set from the motor nameplate rather than from the rating row, because a drive this small is usually protecting a motor rather than controlling a process.
No lifecycle statement and no price is implied. The rating rows, the voltage bands, the enclosure definitions, the terminal and frame data, the filter cable limits, the braking resistor selections and the reactor notes behind 22B-D024F104 are quoted from the drive family's published selection and installation tables.
A PowerFlex 40 order is a single rating code, and the code fixes the current, the frame and the braking resistor at once. The ladder below is the published row set for this supply class, with the resistor the manual names for each kilowatt rating; a resistor carried over from a smaller drive is a different part, not an adequate one.
| Rating code | kW | HP | Output A | Frame | Brake resistor |
|---|---|---|---|---|---|
| 22B-D1P4 | 0.4 | 0.5 | 1.4 | B | 97 ohm, AK-R2-360P500 |
| 22B-D2P3 | 0.75 | 1.0 | 2.3 | B | 97 ohm, AK-R2-360P500 |
| 22B-D4P0 | 1.5 | 2.0 | 4.0 | B | 97 ohm, AK-R2-360P500 |
| 22B-D6P0 | 2.2 | 3.0 | 6.0 | B | 97 ohm, AK-R2-120P1K2 |
| 22B-D010 | 4.0 | 5.0 | 10.5 | C | 77 ohm, AK-R2-120P1K2 |
| 22B-D012 | 5.5 | 7.5 | 12.0 | C | 55 ohm, AK-R2-120P1K2 |
| 22B-D017 | 7.5 | 10.0 | 17.0 | C | 39 ohm, AK-R2-120P1K2 |
| 22B-D024 | 11.0 | 15.0 | 24.0 | C | 24 ohm, AK-R2-120P1K2 with two resistors in parallel |
This code is row 8 of 8 in the class: 11.0 kW (15.0 HP) at 24.0 A continuous output on frame C, with a 24 ohm, AK-R2-120P1K2 with two resistors in parallel braking resistor. The enclosure character on this number reads IP20 flange mount, which is one of the forms the family publishes for this rating: it changes the housing and the drawing, not the current, the frame or the resistor. The code below, 22B-D017, stops at 17.0 A, so a motor between the two currents belongs on this rating rather than on the smaller one.
The frame boundary is where the mechanical answer changes rather than the electrical one: 22B-D6P0 is the last code on frame B at 100 x 180 x 136 mm and 2.2 kg, and 22B-D010 is the first on frame C at 130 x 260 x 180 mm and 4.3 kg. The power terminal moves from 5.3 mm2 (10 AWG) maximum at 1.7-2.2 N-m (16-19 lb-in) to 8.4 mm2 (8 AWG) maximum at 2.9-3.7 N-m (26-33 lb-in) as well, so the motor cable and not only the rail space has to be re-checked at that step.
The class is three-phase in and three-phase out - 22B-D024F104 included - so input and output current differ only by the DC link and the efficiency. A panel fused on the output amps is over-protected on the input side, and one fused on the input amps is under-protected on the motor cable, which is why the two columns are read separately in the manual rather than taken from one row of this table.
Two columns a panel schedule wants for 22B-D024F104 are deliberately absent: branch-circuit protection and the motor protector. They are resolved per rating in the installation tables rather than in this selection ladder, so a quote built from the ladder alone arrives with the current and the frame settled and the fuse holder still open.
Twelve of the 112 22B records carried on this site, ordered by how close their codes sit to this one. This page is 22B-D024F104.
This listing is filed in the AB Drives & Motors group on plc-vip.com; the group index is AB Drives & Motors catalogue index, and the 22B-D024F104 page is one entry in it. Sibling codes of the same group are one click away from that page.