Product Details:
Payment & Shipping Terms:
|
This page documents catalog number 22B-A2P3H204, a PowerFlex 40 drive: 240 V AC single-phase, 2.3 A, 0.4 kW (0.5 HP), enclosure H, frame B. The decode and every figure below come from the drive family's published selection and installation tables; the option positions the documentation does not resolve are named as unresolved rather than guessed.
| Field | Value |
| Catalog number | 22B-A2P3H204 |
| Family (characters 1-3) | 22B - PowerFlex 40 adjustable frequency AC drive |
| Voltage class (character 5) | A - 240 V AC single-phase |
| Input band as published | 200-240 V AC |
| Output as published | 0-230 V three-phase |
| Rating code (characters 6-8) | 2P3 - 2.3 A, 0.4 kW (0.5 HP) |
| Frame size | B |
| Enclosure (character 9) | H - IP20 replacement plate drive |
| Emission class (character 11) | 0 - no integral filter (unfiltered drive) |
| Drive type (character 12) | 4 - the family notes that this position indicates drive type and that all PowerFlex 40 drives carry RS485 |
The 240 V single-phase class is the answer to a machine that has to run without a three-phase supply. Four codes cover 2.3 A to 12 A and 0.4 to 2.2 kW, and the output is a three-phase waveform the motor cannot distinguish from a three-phase feed.
Single-phase input changes the wiring, not the motor. The rectifier draws from two conductors, so the supply cable and the upstream protection are sized single-phase while the motor cable stays a three-phase run. That asymmetry is where most installation mistakes on this class begin.
The enclosure character reads H, which the drive's selection table gives as the IP20 replacement plate drive variant, a form intended for a drive that replaces an existing unit on a mounting plate rather than for a new panel build.
A replacement plate variant is a fit-to-existing-hardware decision before it is an electrical one. The mounting interface and the space it occupies are properties of this variant, so a substitution toward or away from it changes the mechanical installation even when the rating is identical.
On frame B of 22B-A2P3H204 the published power terminal block accepts 5.3 mm2 (10 AWG) maximum and 1.3 mm2 (16 AWG) minimum at 1.7-2.2 N-m (16-19 lb-in), and the I/O terminal block common to frames B and C accepts 1.3 mm2 (16 AWG) maximum and 0.2 mm2 (24 AWG) minimum at 0.5-0.8 N-m. The frame measures 100 x 180 x 136 mm and ships at 2.2 kg.
The emission character reads 0. At 1 the string describes a drive with the integral S-type EMC filter the family lists for this rating; at 0 it describes an unfiltered drive, and the EMC obligation moves to the installation. The manual also gives the cable lengths the two filter families allow: S type for at least 10 m in a Class A environment and 1 m in Class B, L type for at least 100 m in Class A and 5 m in Class B. A filter is not inferable from the power rating, only from this character, which is why 22B-A2P3H204 is read at that position before anything else.
The enclosure does not upgrade the drive; it carries the rating of the enclosure around it, and 22B-A2P3H204 is no exception. The manual states that the drive meets IP40, IP54 and IP65 for NEMA 1, 12, 4 and 4X only when installed inside an enclosure of like rating, which is the sentence that decides whether an open drive is acceptable in a given room.
Dynamic braking on 22B-A2P3H204 is a resistor selection rather than a drive setting: the manual lists 48 ohm, AK-R2-091P500 for this kW rating, and the resistors are rated for 5 percent duty cycle. The resistance changes with the rating rather than staying fixed, so a resistor carried over from a different size does not transfer.
Where the drive needs a line reactor or a DC bus inductor, the manual lists the Bulletin 1321-3R series and the MTE RB series by drive rating, and the larger ratings of the 480 V class are flagged as requiring an external DC bus inductor or AC line reactor rather than being usable bare. For 22B-A2P3H204 the reactor line therefore stays a bill-of-materials question rather than a commissioning note.
The string settles voltage class, output current, enclosure, filter and drive type. It does not settle the motor, the cable, the upstream protection or the duty, and on a drive of this size those four decide whether the installation works. 22B-A2P3H204 is the drive's capability; the installation around it is the engineer's.
Two drives of this family can share a current and a voltage and differ in enclosure or filter, so a spare order that quotes a rounded-off number can produce a unit that runs the motor and does not fit the panel. 22B-A2P3H204 is one of those strings, and quoting it in full is the discipline that prevents that.
The interface position in 22B-A2P3H204 reads 2. The family carries an interface module code in that position, and every PowerFlex 40 drive is stated to include RS485 communication regardless of it, so the RS485 link is a property of the drive rather than of the option. The 2 value is not translated into a module type on this page, because the selection table resolves it per rating and the position is not self-describing.
Commissioning a drive of this class starts with the two numbers the string does not carry: the motor nameplate current, which the drive must be limited to, and the acceleration the machine actually needs. On 22B-A2P3H204 the current limit is set from the motor nameplate rather than from the rating row, because a drive this small is usually protecting a motor rather than controlling a process.
No lifecycle statement and no price is implied. The rating rows, the voltage bands, the enclosure definitions, the terminal and frame data, the filter cable limits, the braking resistor selections and the reactor notes behind 22B-A2P3H204 are quoted from the drive family's published selection and installation tables.
The class is selected by current, not by frame, and the table below shows why: two codes can share a frame and differ by a factor of two in current, and the resistor changes even inside one frame. The rows are the published values for this class; the resistor cell is the part the manual names for that kilowatt rating.
| Rating code | kW | HP | Output A | Frame | Brake resistor |
|---|---|---|---|---|---|
| 22B-A2P3 | 0.4 | 0.5 | 2.3 | B | 48 ohm, AK-R2-091P500 |
| 22B-A5P0 | 0.75 | 1.0 | 5.0 | B | 48 ohm, AK-R2-091P500 |
| 22B-A8P0 | 1.5 | 2.0 | 8.0 | B | 48 ohm, AK-R2-091P500 |
| 22B-A012 | 2.2 | 3.0 | 12.0 | C | 32 ohm, AK-R2-047P500 |
This code is row 1 of 4 in the class: 0.4 kW (0.5 HP) at 2.3 A continuous output on frame B, with a 48 ohm, AK-R2-091P500 braking resistor. The enclosure character on this number reads IP20 replacement plate drive, which is one of the forms the family publishes for this rating: it changes the housing and the drawing, not the current, the frame or the resistor. The next code, 22B-A5P0, is 5.0 A on frame B. It is the smallest rating the class publishes.
The mechanical step in this ladder is the B to C frame change, at 22B-A8P0 (100 x 180 x 136 mm, 2.2 kg) against 22B-A012 (130 x 260 x 180 mm, 4.3 kg). The terminal block follows the frame rather than the current: 5.3 mm2 (10 AWG) maximum at 1.7-2.2 N-m (16-19 lb-in) on B, 8.4 mm2 (8 AWG) maximum at 2.9-3.7 N-m (26-33 lb-in) on C, so the wire size and the torque value both move with the frame.
This is a single-phase class whose output is three-phase from 0 to 230 V: the drive converts phase as well as frequency. That is why a 120 V or 240 V single-phase feed can run an ordinary three-phase motor, and it is also why the current on this ladder is an output current - the input current on a single-phase feed is higher for the same kilowatts, and the feeder is sized from the installation tables rather than from this column.
What the ladder leaves out for 22B-A2P3H204 is the upstream protection. Fuse size and motor protector are per-rating entries in the installation tables, so two drives with the same frame and different current codes take different protection - the frame tells you the terminal, never the fuse.
Twelve of the 112 22B records carried on this site, ordered by how close their codes sit to this one. This page is 22B-A2P3H204.
This listing is filed in the AB Drives & Motors group on plc-vip.com; the group index is AB Drives & Motors catalogue index, and the 22B-A2P3H204 page is one entry in it. Reach it directly if the suffix on this record still needs confirming against a sibling.
Sources. Rockwell publishes the PowerFlex 40 user manual as 22B-UM001, and the technical data for the PowerFlex 4 and 40 ranges as 22-TD001. The ratings, terminal designations and ordering characters quoted on this page for 22B-A2P3H204 follow those two publications.