Product Details:
Payment & Shipping Terms:
|
| 1747-L511 | SLC 5/01 1K Controller | IN STOCK |
| 1747-L514 | SLC 5/01 4K Controller | IN STOCK |
| 1747-L524 | SLC 5/02 4k Controller | IN STOCK |
| 1747-L531 | SLC 5/03 8K Controller | IN STOCK |
| 1747-L532 | SLC 5/03 16K Controller | IN STOCK |
| 1747-L533 | SLC 5/03 32K Controller | IN STOCK |
| 1747-L541 | SLC 5/04 16K Controller | IN STOCK |
| 1747-L543 | SLC 5/04 64K Controller | IN STOCK |
| 1747-L551 | SLC 5/05 16K Controller | IN STOCK |
| 1747-L552 | SLC 5/05 32K Controller | IN STOCK |
| 1747-L553 | SLC 5/05 64K Controller | IN STOCK |
| 1747-M1 | SLC EEPROM Memory Module | IN STOCK |
| 1747-M13 | SLC 64KB Memory Module | IN STOCK |
| 1747-M15 | SLC EEPROM Memory Module Adaptor | IN STOCK |
| 1747-M2 | SLC 4KB Memory Module | IN STOCK |
| 1747-M3 | UVPROM MEMORY MODULE | IN STOCK |
| 1747-NP1 | SLC Wall Mounting Power Supply | IN STOCK |
| 1747-OS302 | SLC 5/03 Firmware Upgrade Kit | IN STOCK |
| 1747-OS401 | SLC 5/04 Firmware Upgrade Kit | IN STOCK |
| 1747-PIC | SLC RS-232 to DH 485 Interface Converter | IN STOCK |
| 1747-PSD | SLC Program Storage Device | IN STOCK |
The 1747-L532 is the 16K member of the SLC 5/03 processor line. It sits in a 1746 chassis, is powered by a 1746-P1 to P7 supply, and controls up to 4,096 input and output points across the local chassis and remote I/O.
What separates a 5/03 from the older 5/01 and 5/02 is the second communication channel: a built-in DH-485 port for the network, plus an RS-232 channel 0 that can run DF1 full-duplex, DF1 half-duplex master or slave, DF1 radio modem, DH-485 as a second channel, Modbus RTU master, or ASCII. Online programming - editing the program while the machine runs - is part of the 5/03 feature set, and so is channel-to-channel passthru between DH-485 and DF1, which is how many panels and PCs reach an SLC network without extra hardware.
The three 5/03 catalogue numbers differ only in memory: 1747-L531 is 8K, this 1747-L532 is 16K, and 1747-L533 is 32K words. Everything else - instruction set, ports, I/O capacity - is common, so the choice is a program-size decision rather than a capability decision.
|
Application
|
controller
|
|
Brand Name
|
PLC Module
|
|
Cat Num
|
1747-L532
|
|
Communication
|
DF1 full/half duplex, DF1 radio modem, DH-485, Modbus RTU master, ASCII |
|
Communication Ports
|
Channel 0 RS-232, Channel 1 DH-485 |
|
Class
|
Central processing unit CPU processors
|
|
Enclosure
|
None (open-style)
|
|
Display
|
Status LEDs
|
|
Memory
|
16K words (user configurable between program and data) |
|
Memory Size
|
16 K words |
|
Mounting
|
Chassis
|
|
Operating Temperature
|
0...60 C (32...140 F)
|
|
Processor
|
SLC 5/03 Controller, 16K memory, up to 4096 I/O points |
|
Power Supply
|
1746-P1 to 1746-P7
|
|
Sub Brand
|
SLC
|
|
Standard
|
GOST,KC,MARINE
|
|
UNSPSC
|
32151705
|
|
Type
|
Modular Controller
|
Memory is 16 K words, user configurable between program storage and data storage - the split is a configuration choice, not a fixed partition. The processor memory table in 1747-UM011 lists the 5/03 range as 8 K, 16 K and 32 K words with 4,096 discrete I/O points, and an EEPROM module can be fitted for program backup: 1747-M13 supports up to 64 K of user-memory backup on 5/03 series C processors running OS302 or later.
Channel 0 is a 9-pin D-shell RS-232 port with a minimum of 500 V dc isolation between the I/O signals and the processor's logic ground - the figure worth quoting when a laptop or a third-party device is connected to a cabinet that also carries drives. Protocol support on this channel is DF1 full-duplex (point-to-point, direct or by modem), DF1 half-duplex master and slave for SCADA-style multipoint links, DH-485 (as a second DH-485 channel via a 1761-NET-AIC and a 1747-CP3, 1761-CBL-AC00 or 1761-CBL-AP00 cable), Modbus RTU master, ASCII for bar-code readers, printers and scales, and DF1 radio modem. Channel-to-channel passthru and remote I/O passthru are listed among the 5/03 features.
Programming connections differ by processor and are documented in the same manual: for the 5/03, a 1747-CP3 cable from channel 0 to a PC serial port, a 1747-UIC USB converter, or a 1784-PKTX(D)/PCMK interface on the network side. Status indicators are labelled RUN, FAULT, FORCE, DH-485 and RS-232 - the DH-485 LED on a 5/03 becomes the DH+ LED on a 5/04, which is the quickest way to tell the two apart in a panel.
We Could Supply Full Range Of PLC Module.
If you find the PLC Module part that you are looking for, pls Skype / Email us for a quote.
Check three things before ordering: the chassis and power supply (a 1746-P1 to P7 supply is required and the processor draws from the backplane), the memory your existing program actually uses - 16 K words is the middle option, and a program that has grown against an 8K 1747-L531 is the usual reason to move to this part - and whether the network is DH-485 or DH+. If the plant runs Data Highway Plus, the processor to specify is the 5/04, not this one.
Support parts for this processor include the 1747-BA lithium battery for RAM backup, the 1747-M13 EEPROM module, the 1747-PSD program storage device, and the 1746-P1...P7 chassis power supplies. All specifications on this page are from the SLC 500 Modular Hardware Style user manual, publication 1747-UM011.
Same-family catalog numbers: 1747-L511, 1747-L514, 1747-L524, 1747-L531. Each of those catalogue numbers has its own stock page on this store; this page covers what differs in the 1747 family.
Other SLC 500 processors and 1746 I/O modules are listed on our Allen-Bradley SLC 500 Systems 1746 and SLC 500 Systems 1747 category pages. Quotes: sales@plc-vip.com.