Product Details:
Payment & Shipping Terms:
|
| 1747-L511 | SLC 5/01 1K Controller | IN STOCK |
| 1747-L514 | SLC 5/01 4K Controller | IN STOCK |
| 1747-L524 | SLC 5/02 4k Controller | IN STOCK |
| 1747-L531 | SLC 5/03 8K Controller | IN STOCK |
| 1747-L532 | SLC 5/03 16K Controller | IN STOCK |
| 1747-L533 | SLC 5/03 32K Controller | IN STOCK |
| 1747-L541 | SLC 5/04 16K Controller | IN STOCK |
| 1747-L543 | SLC 5/04 64K Controller | IN STOCK |
| 1747-L551 | SLC 5/05 16K Controller | IN STOCK |
| 1747-L552 | SLC 5/05 32K Controller | IN STOCK |
| 1747-L553 | SLC 5/05 64K Controller | IN STOCK |
| 1747-M1 | SLC EEPROM Memory Module | IN STOCK |
| 1747-M13 | SLC 64KB Memory Module | IN STOCK |
| 1747-M15 | SLC EEPROM Memory Module Adaptor | IN STOCK |
| 1747-M2 | SLC 4KB Memory Module | IN STOCK |
| 1747-M3 | UVPROM MEMORY MODULE | IN STOCK |
| 1747-NP1 | SLC Wall Mounting Power Supply | IN STOCK |
| 1747-OS302 | SLC 5/03 Firmware Upgrade Kit | IN STOCK |
| 1747-OS401 | SLC 5/04 Firmware Upgrade Kit | IN STOCK |
| 1747-PIC | SLC RS-232 to DH 485 Interface Converter | IN STOCK |
| 1747-PSD | SLC Program Storage Device | IN STOCK |
The 1747-L541 is the 16K SLC 5/04 processor. It mounts in a 1746 chassis, runs from a 1746-P1 to P7 power supply, controls up to 4,096 I/O points, and carries two communication channels: RS-232 on channel 0 and Data Highway Plus on channel 1.
DH+ is the reason to buy a 5/04 rather than a 5/03. On plants where PLC-5 processors, PanelView terminals, older SLC 5/03s and drives already share a Data Highway Plus link, this processor joins that network natively instead of bridging through an AIC+ or a gateway. Channel 0 then stays free for a programming terminal, an ASCII device or a Modbus RTU master link.
The 5/04 line offers 16 K, 32 K and 64 K words - 1747-L541, 1747-L542 and 1747-L543. As with the 5/03 family, the catalogue number is a memory decision; the ports and instruction set are the same across the three.
|
Application
|
controller
|
|
Brand Name
|
PLC Module
|
|
Cat Num
|
1747-L541
|
|
Communication
|
DF1 full/half duplex, DF1 radio modem, DH-485, Modbus RTU master, ASCII, DH+ |
|
Communication Ports
|
Channel 0 RS-232, Channel 1 Data Highway Plus (DH+) |
|
Class
|
Central processing unit CPU processors
|
|
Enclosure
|
None (open-style)
|
|
Display
|
Status LEDs
|
|
Memory
|
16K words (user configurable between program and data) |
|
Memory Size
|
16 K words |
|
Mounting
|
Chassis
|
|
Operating Temperature
|
0...60 C (32...140 F)
|
|
Processor
|
SLC 5/04 Controller, 16K memory, up to 4096 I/O points |
|
Power Supply
|
1746-P1 to 1746-P7
|
|
Sub Brand
|
SLC
|
|
Standard
|
GOST,KC,MARINE
|
|
UNSPSC
|
32151705
|
|
Type
|
Modular Controller
|
Channel 0 is the same RS-232 port as on the 5/03: 9-pin D-shell, at least 500 V dc isolation from logic ground, supporting DF1 full-duplex, DF1 half-duplex master and slave, DH-485, Modbus RTU master and ASCII. Channel 1 is DH+, with its own status LED - on a 5/04 the LED that reads DH-485 on a 5/03 is labelled DH+ here. Duplicate node addresses on the link are reported by a flashing red DH+ indicator, which is the single most useful diagnostic when a network that used to work stops talking after a processor swap.
Memory is 16 K words, configurable between program and data. The processor table lists the whole 5/04 range at 16 K, 32 K and 64 K words with 4,096 discrete I/O points, and the memory module note in the manual allows a 1747-M13 EEPROM for up to 64 K of user-memory backup on 5/04 series C processors at OS501 or later. Firmware is field-upgradable through the 1747-OS401 kit listed for this processor family.
Because the 5/04 is a modular processor, its physical envelope comes from the chassis, not from the card: a 1746-A4, A7, A10 or A13 chassis with the appropriate 1746-P supply. Programming is through channel 0 with a 1747-CP3 cable, a 1747-UIC converter or a 1784-PKTX(D)/PCMK interface, exactly as documented for the 5/04 in 1747-UM011.
We Could Supply Full Range Of PLC Module.
If you find the PLC Module part that you are looking for, pls Skype / Email us for a quote.
Replacing a 5/04 with this part keeps the DH+ address, the channel 0 protocol and the memory size unchanged when the original was a 16K unit. Moving from a 5/03 to a 5/04 changes the network layer, not the program: the ladder logic, I/O addressing and 1746 module layout stay the same, which is what makes this a practical retrofit when a plant standardises on DH+.
Support parts: 1747-BA battery, 1747-M13 EEPROM, 1747-PSD program storage device, 1747-OS401 firmware kit, and the 1746-P1...P7 chassis supplies. All figures here are from the SLC 500 Modular Hardware Style user manual, 1747-UM011.
Same-family catalog numbers: 1747-L511, 1747-L514, 1747-L524, 1747-L531. Each of those catalogue numbers has its own stock page on this store; this page covers what differs in the 1747 family.
SLC 5/04 processors, 1746 I/O modules and chassis are on our SLC 500 Systems 1747 page. Availability: sales@plc-vip.com.