Product Details:
Payment & Shipping Terms:
|
| 1747-ACN15 | SLC ControlNet Adaptor | IN STOCK |
| 1747-ACNR15 | SLC ControlNet Adapter Redundant | IN STOCK |
| 1747-AENTR | SLC 500 Ethernet/IP Adapter | IN STOCK |
| 1747-AIC | SLC Isolated Link Coupler | IN STOCK |
| 1747-ASB | SLC Remote I/O Adapter Module | IN STOCK |
| 1747-BA | SLC Lithium Battery | IN STOCK |
| 1747-BSN | SLC Backup Scanner Module | IN STOCK |
| 1747-C10 | SLC Replacement Cable | IN STOCK |
| 1747-C11 | SLC Replacement Cable | IN STOCK |
| 1747-C13 | SLC Cable | IN STOCK |
| 1747-C20 | SLC Replacement Cable | IN STOCK |
| 1747-CP3 | SLC 5/03 Programmer RS-232 Cable | IN STOCK |
| 1747-DCM | SLC Direct Communication Module | IN STOCK |
| 1747-DEMO-7 | SLC Demo Kit | IN STOCK |
| 1747-DPS1 | SLC Port Splitter | IN STOCK |
| 1747-DPS2 | SLC Configurable Port Splitter | IN STOCK |
| 1747-DU501 | SLC 5/05 Firmware Upgrade Kit | IN STOCK |
| 1747-KE | SLC Communication Interface Module | IN STOCK |
| 1747-KFC15 | SLC Interface Module | IN STOCK |
The 1747-AENTR is the adapter that lets a CompactLogix or ControlLogix controller own a rack of SLC 1746 I/O over EtherNet/IP. Physically it takes the controller's place in slot 0 of an SLC chassis and acts as a gateway between the 1746 backplane and the network - the migration route for a plant that wants a modern controller without rewiring an installed I/O rack.
It replaces, in the same slot, an SLC processor, or on a remote rack a 1747-ASB or the ControlNet adapters 1747-ACN15/ACNR15. That is precisely why this part still has a market: a line whose panels, field wiring and terminal blocks are sound but whose SLC 5/05 is obsolete can be re-controlled without touching a single conductor.
Its lifecycle is now part of the buying decision: the 1747-AENTR is at end of life and no longer sold new. Anyone specifying it today is either holding a migration already in progress or buying a spare for an installed system - and both cases need the electrical and connection facts below, not a brochure.
|
Brand Name
|
PLC Module
|
|
Cat Num
|
1747-AENTR
|
|
Communication
|
EtherNet/IP adapter, slot 0 of an SLC 500 chassis; gateway between 1746 backplane and EtherNet/IP |
|
Communication Modules
|
EtherNet/IP Communication module
|
|
Connection Cables
|
802.3 compliant shielded or unshielded twisted pair
|
|
Depth
|
130.8mm, 5.15"
|
|
Display
|
Status LEDs
|
|
Enclosure
|
None (open-style)
|
|
Ethernet-IP Communication Rate
|
10/100 Mbps
|
|
Height
|
145.3mm, 5.72"
|
|
Interface
|
2 Ethernet RJ45 ports (embedded switch), 10/100 Mbps, Category 5 |
|
Logix Communication Connections
|
128
|
|
Mounting
|
Chassis
|
|
Number Of Channels
|
2
|
|
Operating Temperature
|
0...60 C (32...140 F)
|
|
Standard
|
CE,C-TICK,CUL,KC,UL
|
|
Sub Brand
|
SLC
|
|
TCP-IP Communication Connections
|
64
|
|
Type
|
SLC 500 EtherNet/IP adapter for Logix migration; end of life, no longer for sale |
|
UNSPSC
|
32151705
|
|
Width
|
34.8mm, 1.37"
|
Network: two RJ45 ports configured as an embedded switch, 10/100 Mbps half or full duplex, Category 5 shielded or unshielded twisted pair, topologies star, tree, daisy-chain/linear and ring. Address selection by the network switches (001...254, switch setting 888 restores factory defaults) or DHCP, which is enabled by default.
Connections: one exclusive owner connection per SLC module; up to 5 input-only and 5 listen-only connections per module; up to 5 explicit messaging connections to the adapter; up to 5 consumers per multicast connection. On firmware 2.001 and later it additionally supports direct connections to rack extensions, up to 96 Class 1 and 8 Class 3. Rack and partial-set connections are not supported on firmware 1.001 - a detail that matters when a spare arrives with the wrong revision.
Backplane: 470 mA at 5 V dc, thermal dissipation 2.49 W (8.50 BTU/hr), isolation 50 V continuous basic insulation, 145.3 x 34.8 x 130.8 mm, 168 g, open-style, temperature code T3C, wiring category 1 on the communication ports. The chassis must be powered by a 1746-P1...P7 supply; the 1746-P4 must not be used in UL Class 1 Division 2 locations.
What it will not do: it does not support SLC I/O modules that require G files, and it does not support communication modules in the same chassis. Only one 1747-AENTR may be installed per rack and its connected rack extensions. Those three exclusions are the difference between a migration plan that works and one that stalls at the first 1746 module that turns out to be a specialty card.
We Could Supply Full Range Of PLC Module.
If you find the PLC Module part that you are looking for, pls Skype / Email us for a quote.
Two settings decide whether the migrated rack behaves: enable "Major Fault On Controller If Connection Fails While in Run Mode" on the adapter and on the 1746 modules, and accept that on connection establishment the outputs go to their Idle state before Run - which on a running machine means the migration window is a shutdown, not a hot swap.
Class 3 explicit requests to a specific 1746 module may time out, with the adapter returning an error code rather than a silent failure. If an HMI polls individual modules directly, that behaviour has to be designed for.
Specifications are from publications 1747-IN521 (installation) and 1747-UM076 (user manual); connection limits from the module's firmware documentation, including release notes 1747-RN656.
SLC 500 processors, 1746 I/O and 1747 adapters are listed on our Allen-Bradley SLC 500 1747 and SLC 500 1746 I/O category pages. Spare availability: sales@plc-vip.com.