Product Details:
Payment & Shipping Terms:
|
| 1768-CNB | CompactLogix L4X ControlNet Module | IN STOCK |
| 1768-CNBR | CompactLogix Redundant ControlNet Module | IN STOCK |
| 1768-ENBT | CompactLogix L4X EtherNet/IP Module | IN STOCK |
| 1768-EWEB | CompactLogix Enhanced Web Server Module | IN STOCK |
| 1768-KY1 | CompactLogix L43/L45 Replacement Key | IN STOCK |
| 1768-L43 | CompactLogix L43 Processor | IN STOCK |
| 1768-L43S | Compact GuardLogix CPU L43S 2M/.5M | IN STOCK |
| 1768-L45 | CompactLogix Controllers L45 | IN STOCK |
| 1768-L45S | Compact GuardLogix CPU L45S 3M/1M | IN STOCK |
| 1768-M04SE | CompactLogix Motion Module | IN STOCK |
| 1768-PA3 | CompactLogix L4x AC Input Power Supply | IN STOCK |
| 1768-PB3 | CompactLogix L4x DC Input Power Supply | IN STOCK |
The 1768-PA3 is the ac-input power supply for a 1768 CompactLogix backplane (L43/L45 family). It takes 85...265 V ac - or 108...132 V dc on the same terminals - and delivers 24 V dc to the backplane at up to 3.5 A, with a second 24 V dc output at 0.25 A on a front-panel terminal block for field devices.
The architecture is worth understanding before sizing one: the power supply does not feed the controller with 5 V directly. It sends 24 V dc to the controller in slot 0, and the controller converts that to 5 V dc and 24 V dc and distributes it to the 1769 I/O modules on its right and to 1768 communication and motion modules on its left. That is why the power supply's rating is expressed in watts at the backplane rather than in a list of rails.
90 W output, 120 VA/120 W input at full load and 30 W of internal dissipation are the three numbers that drive panel design: the enclosure has to remove 30 W, and the supply has to be derated against 55 °C ambient rather than 25 °C when it sits in a sealed cabinet.
|
Brand Name
|
PLC Module
|
|
Cat Num
|
1768-PA3
|
|
Connection Cables
|
None required
|
|
Display
|
Status LEDs
|
|
Enclosure
|
None (open-style)
|
|
Height
|
131.25 mm (5.17 in); width 132.75 mm (5.23 in); depth 105.50 mm (4.15 in) |
|
Input Voltage
|
85...265V AC (108...132V DC), 120/220V AC nominal, 47...63 Hz |
|
Mounting
|
DIN Rail / Panel Mount
|
|
Operating Temperature
|
0...60 C (32...140 F) |
|
Output Voltage
|
24V DC to backplane (3.5 A) and 24V DC to front terminal block (0.25 A); 90 W output max |
|
Standard
|
CE,C-TICK,CUL,GOST,KC,UL
|
|
Sub Brand
|
CompactLogix
|
|
Type
|
Power Supply
|
|
UNSPSC
|
32151706
|
|
Wattage
|
90 W output max; 120 VA/120 W input max; 30 W dissipation at full load |
|
Width
|
132.75mm, 5.23 in |
Input: 85...265 V ac, 47...63 Hz, nominal 120/220 V ac, with a dc alternative of 108...132 V dc across the same terminals. Maximum input power is 120 VA/120 W. Inrush is 50 A at 85...132 V ac and 80 A at 195...265 V ac - high enough that the upstream breaker curve and the number of supplies on one circuit have to be checked together, not separately.
Output: 90 W maximum, 6 W minimum, with 24 V dc at up to 3.524 A to the backplane and 24 V dc at 0.25 A on the user-accessible terminal block, regulated to 18...27.6 V. The auxiliary output is disabled during hold-up, which is deliberate: field devices are dropped first so the controller and its memory keep the last usable seconds of power.
Ride-through and hold-up: minimum ride-through 25 ms at 90 W for this ac unit, full-power hold-up 5 ms at 90 W, and an extended hold-up interval of 8...12 s at 1.25 W - the window in which the controller can write its retentive data. Isolation is 250 V reinforced between input and system and between input and the 24 V dc auxiliary, type tested at 4250 V dc for 60 s; the auxiliary-to-system barrier is 150 V basic, tested at 2200 V dc for 60 s. Recommended external overcurrent protection is 4...6 A; the internal fuse is soldered and not replaceable, so a crowbar fault means a new supply.
We Could Supply Full Range Of PLC Module.
If you find the PLC Module part that you are looking for, pls Skype / Email us for a quote.
Mechanics: 131.25 x 132.75 x 105.50 mm, 0.98 kg, DIN rail or panel mount, mounting screw torque 1.16 N·m (10 lb·in) with M4 or #8 screws, terminal torque 0.6 N·m (5 lb·in). Input conductors 2.5 mm² (14 AWG) copper rated 75 °C or higher; output conductors 2.5...0.25 mm² (14...22 AWG). Enclosure open-style, North American temperature code T4, wiring category 1 on power ports.
The choice between PA3 and PB3 is a supply decision, not a preference: PA3 accepts plant ac, PB3 takes 24 V dc (16.8...31.2 V dc) and dissipates less - 22 W at full load instead of 30 W. In a cabinet that is already thermally tight, PB3 off a bulk 24 V supply is often the better arrangement; where no dc bus exists, PA3 avoids adding one.
One sizing rule from the publication: 1768 modules have no distance rating from the power supply, but 1769 I/O modules on the right of the controller are distance-rated from the controller, not from the supply. Counting slots without counting that distance rating is how a backplane ends up with modules that will not communicate.
All values on this page are from publication 1769-TD008, CompactLogix Power Supplies Specifications.
CompactLogix controllers and 1769 I/O are listed on our Allen-Bradley CompactLogix 1769 category page. Quotes: sales@plc-vip.com.