The 1734-AENTR is the dual-port EtherNet/IP adapter for POINT I/O: two RJ45 ports in an embedded switch, so a slice can be daisy-chained, star- or tree-connected, or closed into a device-level ring. It is the adapter that makes a POINT I/O island a first-class citizen on a modern line network rather than a spur hanging off a switch.
Its practical capacity: up to 63 POINT I/O modules, 5 rack-optimized (or enhanced rack-optimized) connections and 31 direct connections, with 0.8 A of POINTBus output at 5 V dc to feed the slices. The 0.8 A is the number that decides the island layout - a slice of digital modules is comfortable inside it, but analog and specialty modules draw 75...220 mA each, and the honest way to design the island is to add up the POINTBus current before adding the twentieth module, not after.
The adapter also supplies field power: 24 V dc in at 10 A maximum, 9 A back out to the slices, and the DC-DC converter on the base generates the 5 V POINTBus rail. Two status LEDs on the base report link 1 and link 2 separately - which is the ring diagnostic an operator actually needs, because a ring that has healed still shows one dark port.
|
Application
|
POINT I/O adapter for EtherNet/IP; 24V DC field power 10...28.8V DC @ 10 A in, 9 A out |
|
Brand Name
|
PLC Module
|
|
Cat Num
|
1734-AENTR
|
|
Communication Protocol
|
EtherNet/IP
|
|
Enclosure
|
None (open-style)
|
|
Mounting
|
Din-rail
|
|
Power Supply
|
24V DC @ 10 A input, 10...28.8V DC; consumption 10.4 W max, dissipation 6.3 W @ 28.8V DC |
|
Special Features
|
Device Level Ring
|
|
Standard
|
CE,C-TICK,CUL,GOST,KC,MARINE,UL
|
|
Sub Brand
|
POINT I/O
|
|
Temperature Rating
|
-20 to 55 C (-4 to 131 F)
|
|
Type
|
POINT I/O dual-port EtherNet/IP adapter, 63 modules max, 0.8 A POINTBus output, 31 direct + 5 rack-optimized connections |
|
UNSPSC
|
32151701
|
Power: 10.4 W maximum consumption at 28.8 V dc, 6.3 W maximum dissipation (21.5 BTU/hr), field supply 10...28.8 V dc at 10 A in and 9 A out, module input 10...28 V dc at 1,000 mA, POINTBus output 5 V dc at 0.8 A maximum. Reverse-polarity protected, and the output holds within specification through a 10 ms input dropout at 10 V with maximum load - relevant where the 24 V rail is shared with contactor coils.
Isolation: 50 V continuous, reinforced insulation between all circuits, type tested at 500 V ac for 60 s. That is a functional-isolation figure, not a safety-isolation one: it separates the field side from the network for noise purposes and does not make the adapter a safety barrier.
Mechanics: 79.8 x 73.8 x 133.1 mm (H x W x D), open-style, 35 mm DIN rail, mounted as the leftmost (starter) module of the slice, temperature code T4, operating -20...55 °C, non-operating -40...+85 °C, 5...95% non-condensing, 5 g vibration at 10...500 Hz. Address selection is by the three-position thumbwheel (001...254, with 801...864 setting chassis size on firmware 5.015 and later), or DHCP/BOOTP.
Addressing: with the thumbwheel set to 001...254 the adapter takes 192.168.1.xxx with mask 255.255.255.0; when the switches sit on an invalid value it falls back to DHCP/BOOTP, and 888 restores factory defaults. The same thumbwheel sets chassis size (801...864 on firmware 5.015+), which is the second reason a like-for-like firmware match matters on a replacement - a chassis-size mismatch shows up as missing slices, not as a network fault.
Backplane extension: to exceed 0.8 A, add 1734-EP24DC or 1734-EPAC extension power supplies - each extends the POINTBus, and several are needed to reach the 63-module maximum. Design the island with the extension supplies in the plan, not as a field fix.
We Could Supply Full Range Of PLC Module.
If you find the PLC Module part that you are looking for, pls Skype / Email us for a quote.
The choice between 1734-AENT and 1734-AENTR is not port count alone. The single-port 1734-AENT supplies 1.0 A of POINTBus current against 0.8 A on the AENTR, so a dense island with analog modules may fit an AENT and not an AENTR - and moving to a ring may then require re-planning the island power, which is exactly the surprise to avoid mid-project.
What a replacement must match: Series (C), firmware revision, and the chassis-size thumbwheel convention. The Series C adapter uses the 801...864 chassis-size settings; an older series in the same island can have different conventions, and a mixed pair is a commissioning problem rather than a parts problem.
Specifications are from publication 1734-IN041, POINT I/O Dual-port EtherNet/IP Adapter, Series C, and publication 1734-UM017 for configuration.
Same-family catalog numbers: 1734-AENT. Each of those catalogue numbers has its own stock page on this store; this page covers what differs in the 1734 family.
POINT I/O adapters, slices, terminal bases and extension power modules are listed on our Allen-Bradley POINT I/O 1734 category page. Stock and lead time: sales@plc-vip.com.