Product Details:
Payment & Shipping Terms:
|
| 1762-OA8 | MicroLogix 8 Point Digital Output Module | IN STOCK |
| 1762-OB16 | MicroLogix 16 Point D/O Module | IN STOCK |
| 1762-OB32T | MicroLogix 32 Point D/O Module | IN STOCK |
| 1762-OB8 | MicroLogix 8 Point Digital Output Module | IN STOCK |
| 1762-OF4 | MicroLogix 4 Point Analog Output Module | IN STOCK |
| 1762-OV32T | MicroLogix 32 Point Module | IN STOCK |
| 1762-OW16 | MicroLogix 16 Point Relay | IN STOCK |
| 1762-OW8 | MicroLogix 8 Point Relay Output Module | IN STOCK |
| 1762-OX6I | MicroLogix 6 Point Relay Output Module | IN STOCK |
| 1762-RPLDR2 | MicroLogix Replacement Part | IN STOCK |
| 1762-RPLRTB40 | MicroLogix 40 Point Replacement TB | IN STOCK |
| 1762-RTC | MicroLogix 1200 Real Time Clock | IN STOCK |
The 1762-OW16 is the 16-point relay output expansion module for MicroLogix 1200 and 1500 controllers. Sixteen normally-open relay contacts are divided into two isolated groups of eight, with a maximum total controlled load of 1440 VA per module - the highest of any 1762 discrete output module, and the reason this part is still the default when a panel drives a mixed list of ac contactors, dc valves and signal relays.
Its siblings in the same family cover the other output cases: 1762-OB16 and 1762-OB32T are solid-state 24 V dc outputs, 1762-OA8 is an 8-point ac output, 1762-OW8 and 1762-OX6I are smaller relay modules. Where the load is purely dc and switching speed matters, a solid-state module is the better choice; where the load list is mixed or the destination voltage is not yet fixed, dry contacts are.
Physically it is the standard 1762 slice - 90 x 40.4 x 87 mm, 285 g, DIN rail or panel mount - so a controller can carry seven of these alongside input and analog modules without changing the enclosure.
|
Brand Name
|
PLC Module
|
|
Cat Num
|
1762-OW16
|
|
Class
|
Programmable Logic Controller Module
|
|
Depth
|
87
|
|
Digital Output Modules
|
16 Point VAC/VDC Relay Output Module
|
|
Enclosure
|
IP20
|
|
Height
|
90
|
|
I-O Isolation
|
Isolated
|
|
I-O Status Indication
|
LED
|
|
Module Interfaces
|
relay output
|
|
Mounting
|
DIN Rail, Panel Mount
|
|
Number Of Channels
|
16 relay outputs, 2 isolated groups of 8, 1440 VA total |
|
Standard
|
C-TICK,GOST,KC,MARINE
|
|
Sub Brand
|
MicroLogix 1200
|
|
Temperature Rating
|
-20-65 C
|
|
Type
|
Discrete, Output
|
|
UNSPSC
|
32151601
|
|
Voltage Rating
|
5...265V AC / 5...125V DC |
|
Width
|
40
|
The relay contact table in 1762-IN009 gives the real numbers per pole: at 240 V ac, 7.5 A make / 0.75 A break with 2.5 A continuous per point, 1800 VA make / 180 VA break; at 120 V ac, 15 A make / 1.5 A break with 2.5 A continuous; at 125 V dc, 1.0 A make / 0.22 A break at 28 VA; at 24 V dc, 2.0 A make / 1.2 A break at 28 VA. Continuous current is limited to 8 A per common and 16 A per module, total controlled load 1440 VA, minimum on-state current 10 mA, off-state leakage 0 mA, and signal delay 10 ms on and off into a resistive load. Electrical relay life is 100 x 10³ operations minimum at 3 A 30 V dc or 250 V ac resistive.
For dc loads the publication states the rule directly: the make/break rating is found by dividing 28 VA by the applied dc voltage - 28 VA at 48 V dc gives 0.58 A - and below 14 V dc the contact rating cannot exceed 2 A regardless of the arithmetic. Inductive loads are where relay life is actually lost, so surge suppressors across coils are called for in the same document.
Isolation is documented per group: group 1 is outputs 0...7 and group 2 is outputs 8...15, group-to-backplane verified at 1836 V ac or 2596 V dc for 1 s with 265 V ac working voltage under IEC Class 2 reinforced insulation, and group-to-group at the same test voltage with 150 V ac working voltage under Class 2 reinforced insulation. That means one group can switch 240 V ac contactor coils while the other switches 24 V dc solenoids, with no shared node between them. Bus draw is 140 mA at 5 V dc (0.70 W) plus 180 mA at 24 V dc (4.32 W), maximum heat dissipation 6.1 W, and the derating chart in the publication applies to each output - the 2.5 A per-point figure is not available at every ambient temperature.
We Could Supply Full Range Of PLC Module.
If you find the PLC Module part that you are looking for, pls Skype / Email us for a quote.
Use the 1440 VA module figure as the first constraint, then the 8 A per common and 16 A per module limits, then the 2.5 A per point; a panel full of 240 V ac contactors will hit the common limit before the VA limit in most designs. Keep inductive loads on suppressed coils and separate the ac group from the dc group at the terminal block, which is what the group isolation allows.
All ratings on this page come from the MicroLogix 1762-OW16 Relay Output Module installation instructions, publication 1762-IN009C-EN-P (July 2013).
Same-family catalog numbers: 1762-OW8. Each of those catalogue numbers has its own stock page on this store; this page covers what differs in the 1762 family.
Other 1762 modules, including the 1762-OB16 solid-state output and 1762-IF2OF2 analog combo, are on our Allen-Bradley MicroLogix 1200 1762 page. Quotes: sales@plc-vip.com.