The 1762-IQ16 is the 16-point 24 V dc input expansion module for the MicroLogix 1200 and 1500 platforms. Sixteen inputs are split into two isolated groups of eight, so a machine can mix sinking and sourcing field devices without a common reference problem, and each point has its own diagnostic LED inside the module door.
It belongs to the 1762 family, the expansion line that also includes the 1762-IQ8 and 1762-IQ32T inputs, the 1762-OB16 and 1762-OW16 outputs, the 1762-IF2OF2 analog combo, and the 1762-RTC real-time clock. Any of them installs on the controller's bus with the flat ribbon cable and bus connector, on 35 x 7.5 mm or 35 x 15 mm DIN rail, and the platform accepts up to seven modules.
Where it earns its place is on a machine that has outgrown the controller's embedded 24 V dc points but does not need a platform change. Sixteen inputs in one 40.4 mm wide slice is dense enough to absorb a full sensor bank - proximity switches, photoelectric sensors, pressure and level switches - without adding a second controller or a remote I/O drop.
|
Brand Name
|
PLC Module
|
|
Cat Num
|
1762-IQ16
|
|
Class
|
Programmable Logic Controller Module
|
|
Depth
|
87
|
|
Digital Input Modules
|
16 Point 24 VDC Sink/Source Input Module
|
|
Enclosure
|
IP20
|
|
Height
|
90
|
|
I-O Isolation
|
Isolated
|
|
I-O Status Indication
|
LED
|
|
Module Interfaces
|
digital input
|
|
Mounting
|
DIN Rail, Panel Mount
|
|
Number Of Channels
|
16 inputs, 2 isolated groups of 8 |
|
Standard
|
C-TICK,GOST,KC,MARINE
|
|
Sub Brand
|
MicroLogix 1200
|
|
Temperature Rating
|
-20-65 C
|
|
Type
|
Discrete, Input
|
|
UNSPSC
|
32151601
|
|
Voltage Rating
|
24V DC sink/source (10...30V DC operating) |
|
Width
|
40
|
The documented operating voltage range is 10...30 V dc, with the on-state threshold at 10 V dc minimum and the off-state threshold at 5 V dc maximum, so a standard 24 V dc sensor with a 3 V saturation voltage switches cleanly. On-state current is 2.0 mA minimum at 10 V dc, 8.0 mA nominal at 24 V dc and 12.0 mA maximum at 30 V dc; off-state current is 1.5 mA maximum and nominal input impedance is 3 kΩ. Signal delay is 8.0 ms on and 8.0 ms off - this is a general-purpose input module, not a high-speed counter front end, and the delay figure is what to check when a design assumes the input reacts instantly.
Isolation is per group: group 1 covers inputs 0...7 and group 2 covers inputs 8...15, with group-to-backplane isolation verified at 1200 V ac for 1 s or 1697 V dc for 1 s, at 75 V dc working voltage under IEC Class 2 reinforced insulation. That two-group split is the reason the module is rated sink/source: each group's common can be tied to either side of the field supply, so a panel can carry sinking sensors on one bank and sourcing devices on the other.
Power draw from the bus is 70 mA at 5 V dc (0.35 W), and maximum heat dissipation is 5.4 W at 30 V dc or 4.3 W at 26.4 V dc. Dimensions are 90 x 40.4 x 87 mm (110 mm including mounting tabs), shipping weight approximately 230 g, enclosure IP20, operating temperature -20...65 °C with derating charts above that, and the module carries a T3C North American temperature code. Wiring accepts #14...22 AWG solid or #16...22 AWG stranded Cu-90 °C conductors at 0.90 N·m (8 lb·in); the 1762-IQ16 is North American hazardous-location approved, and the field supply must be Class 2 or limited voltage/current for UL compliance and SELV/PELV for the CE Low Voltage Directive.
We Could Supply Full Range Of PLC Module.
If you find the PLC Module part that you are looking for, pls Skype / Email us for a quote.
Pair it with a 1762-OB16 or 1762-OW16 on the output side if the application is discrete, or with the 1762-IF2OF2 if analog signals are also needed. Inputs that must count pulses or catch short events belong on a high-speed counter module rather than here, because 8 ms filtering is the documented behaviour of this part.