Product Details:
Payment & Shipping Terms:
|
| 1762-IA8 | MicroLogix 8 Point Digital Input Module | IN STOCK |
| 1762-IF2OF2 | MicroLogix 4 Point Analog Comb Module | IN STOCK |
| 1762-IF4 | MicroLogix 4 Point Analog Input Module | IN STOCK |
| 1762-IQ16 | MicroLogix 16 Point Digital Input Module | IN STOCK |
| 1762-IQ32T | MicroLogix 32 Point Digital Input Module | IN STOCK |
| 1762-IQ8 | MicroLogix 8 Point Digital Input Module | IN STOCK |
| 1762-IQ8OW6 | MicroLogix 14 Point Digital Comb Module | IN STOCK |
| 1762-IR4 | MicroLogix 4 Point Module | IN STOCK |
| 1762-IT4 | MicroLogix 4 Point Input Module | IN STOCK |
The 1762-IF2OF2 adds four analog channels to a MicroLogix 1200 or 1500: two differential inputs and two single-ended outputs, each configurable for 0...10 V dc or 4...20 mA. Resolution is 12 bits, and both halves of the module are isolated from the system at 30 V ac/30 V dc working voltage.
In the 1762 family this is the compact analog answer next to the dedicated 1762-IF4 (four inputs), 1762-IR4 (four RTD inputs), 1762-IT4 (four thermocouple inputs) and 1762-OF4 (four outputs). Two in and two out suits a controller that regulates one loop - a pressure or flow loop - while reading one process variable, without paying for eight channels.
One detail decides most applications before any specification does: the input type is chosen by a switch inside the module, not by wiring alone. Switch 1 sets channel 0 and switch 2 sets channel 1, the factory default for both is current, and the switch is reached through the ventilation slots on the top of the housing. A module pulled from stock and wired for voltage without moving those switches will read 4...20 mA ranges, which is the most common commissioning error with this part.
|
Brand Name
|
PLC Module
|
|
Cat Num
|
1762-IF2OF2
|
|
Class
|
Programmable Logic Controller Module
|
|
Current Range
|
4...20 mA |
|
Depth
|
87
|
|
Enclosure
|
IP20
|
|
Height
|
90
|
|
I-O Isolation
|
Isolated
|
|
I-O Status Indication
|
LED
|
|
I-O_Ports
|
2 analog inputs / 2 analog outputs |
|
Input
|
2 differential unipolar, voltage or current, switch selected |
|
Module Interfaces
|
analog combination
|
|
Mounting
|
DIN Rail, Panel Mount
|
|
Number Of Channels
|
4 point
|
|
Output
|
2 single-ended unipolar, voltage or current, terminal selected |
|
Standard
|
C-TICK,GOST,KC,MARINE
|
|
Sub Brand
|
MicroLogix 1200
|
|
Temperature Rating
|
-20-65 C
|
|
Type
|
Analog, Combo
|
|
UNSPSC
|
32151601
|
|
Voltage Rating
|
0...10V DC (full scale 0...10.5V DC) |
|
Width
|
40
|
Inputs are two differential unipolar channels with a successive-approximation converter. Normal operating range is 0...10 V dc or 4...20 mA, with full-scale conversion to 0...10.5 V dc or 0...21 mA and over/under-range flags when the normal range is exceeded. Input impedance is 200 kΩ on the voltage terminal and 250 Ω on the current terminal; common-mode range is ±27 V with common-mode rejection above 55 dB at 50 and 60 Hz; protection is ±30 V on voltage and ±32 mA on current. Non-linearity is ±0.12% of full scale, repeatability ±0.12%, typical overall accuracy ±0.3% of full scale at 25 °C and ±0.55% over -20...65 °C, including offset, gain, non-linearity and repeatability. Channel diagnostics report over-range, under-range and open circuit by bit.
Outputs are two single-ended unipolar channels with a resistor-string D/A converter. Load range is above 1 kΩ on the voltage output and 0...500 Ω on the current output including wire resistance; reactive load limits are below 1 µF on voltage and below 0.1 mH on current. Typical overall accuracy is ±0.5% of full scale at 25 °C and ±1.17% over -20...65 °C, non-linearity below ±0.59%, ripple below ±0.1% from 0...500 Hz, and both open-circuit and short-circuit protection are continuous with ±32 mA output protection. Output type is selected by which terminal is wired - Iout or Vout - together with the type/range bits in the configuration file, so a change from voltage to current is a wiring change, unlike the inputs.
Module-level figures: resolution 12 bits unipolar, dimensions 90 x 40.4 x 87 mm, shipping weight 240 g, bus draw 40 mA at 5 V dc plus 105 mA at 24 V dc, product code 75, wiring category 2 on signal ports, recommended cable Belden 8761 shielded. The input/output group to system isolation is rated 30 V ac/30 V dc working voltage under IEC Class 2 reinforced insulation, type tested at 500 V ac or 707 V dc for 1 minute - that is isolation from the backplane, not channel-to-channel isolation, so both input channels share a common reference.
We Could Supply Full Range Of PLC Module.
If you find the PLC Module part that you are looking for, pls Skype / Email us for a quote.
Wiring accepts up to two wires per terminal: #14...22 AWG solid or #16...22 AWG stranded Cu-90 °C at 0.904 N·m (8 lb·in). Data formats are raw/proportional and scaled-for-PID; input words hold 0...16,380 in PID format, output words 0...32,760 raw or 0...16,380 scaled. Because inputs are differential, a two-wire transmitter can be wired with its supply return on the IN- terminal, and the common-mode range of ±27 V is what allows that arrangement.
Commissioning order: set the two input switches for the actual signal type before power-up, confirm 24 V dc field power and the 30 V isolation rating against the loop supply, then scale in the configuration file. All figures here are from the MicroLogix 1762-IF2OF2 Analog Input/Output Module installation instructions, publication 1762-IN005.
Same-family catalog numbers: 1762-IF4. Each of those catalogue numbers has its own stock page on this store; this page covers what differs in the 1762 family.
The other 1762 analog modules are on our Allen-Bradley MicroLogix 1200 1762 page. Quotes: sales@plc-vip.com.