Product Details:
Payment & Shipping Terms:
|
| 1763-BA | MicroLogix 1100 Battery | IN STOCK |
| 1763-L16AWA | MicroLogix 1100 16 Point Controller | IN STOCK |
| 1763-L16BBB | MicroLogix 1100 16 Point Controller | IN STOCK |
| 1763-L16BWA | MicroLogix 1100 16 Point Controller | IN STOCK |
| 1763-L16DWD | MicroLogix 1100 16 Point Controller | IN STOCK |
| 1763-MM1 | MicroLogix 1100 Memory Module | IN STOCK |
| 1763-NC01 | MicroLogix Cable | IN STOCK |
The 1763-L16BWA is the ac-powered version of the MicroLogix 1100 that takes dc field signals. The controller itself runs from a 120/240 V ac supply, which means it can sit in an existing MCC or panel without a separate 24 V dc power supply, while all ten of its inputs accept 24 V dc from pushbuttons, proximity switches, photo-eyes and safety-relay auxiliary contacts. Six relay outputs are individually isolated, and two 0...10 V dc analog inputs are available on the same brick.
That combination is the reason this part outnumbers the other three variants in retrofit work: most older panels are ac fed, but most modern sensors are dc. Choosing the L16BWA removes the need for an interposing relay panel on the input side while keeping relay outputs that can switch contactor coils and valve solenoids directly. The 1763-L16AWA is the alternative when the field devices are 120 V ac; the 1763-L16DWD and 1763-L16BBB are the alternatives when the panel itself is dc powered.
The footprint is 110 mm wide, 90 mm high and 87 mm deep, DIN rail or panel mounted, IP20, rated -20...+60 °C, with an on-board display and keypad for setting addresses and reading immediate I/O status without a programming terminal.
| Brand Name | PLC Module |
|
Cat Num
|
1763-L16BWA |
|
Communication
|
DF1, DH-485, Modbus RTU, ASCII, EtherNet/IP messaging |
|
Class
|
controller |
|
Depth
|
87 mm |
|
Embedded Analog
|
(2) Voltage Inputs 0...10V DC, 10-bit |
|
Enclosure
|
IP20 |
|
Display
|
Yes |
|
Height
|
90 mm |
|
Input Signal
|
24V DC |
|
Interface
|
Ethernet Port and Isolated RS-232/RS-485 combo port |
|
Memory
|
8 KB |
|
Number Of Channels
|
10 I/P, 6 O/P |
|
Mounting
|
DIN Rail, Panel Mount |
|
Output Signal
|
(6) Relay, individually isolated |
|
Operating Temperature
|
-20... 60 ?C (-4...140 ?F) |
|
Power Supply
|
120/240V AC |
|
Sub Brand
|
MicroLogix 1100 |
|
Special Features
|
Built-in RTC, Online Editing, Up to 4 Expansion I/O |
|
Standard
|
C-TICK,GOST,KC,MARINE |
|
Width
|
110 mm |
|
UNSPSC
|
32151705 |
|
Type
|
Controller |
According to publication 1763-IN001 the dc input groups are: inputs 0 through 3 high-speed, on-state 14...24 V dc (14...30 V dc at 30 °C, 14...26.4 V dc at 65 °C), off-state 0...5 V dc, up to 20 kHz, 3.1 kΩ nominal impedance, 2.5 mA at 14 V dc minimum and 12.0 mA at 30 V dc maximum on-state current. Inputs 4 and higher are the standard group with the same voltage windows, 1 kHz operating frequency, 3.1 kΩ impedance and the same current figures. Off-state leakage is 1.5 mA maximum, which is the number to compare against the leakage rating of two-wire sensors on long cable runs.
The relay outputs carry the full family rating: 240 V ac at 15.0 A make / 1.5 A break with 5.0 A continuous per common, 120 V ac at 30.0 A make / 3.0 A break, 125 V dc at 0.22 A make / 1.0 A break at 28 VA, 10 mA minimum load current, 10 ms maximum turn-on and turn-off, and 10,000,000 mechanical cycles. In Class I, Division 2 areas the maximum controlled load for this catalogue number is 720 VA. Because the outputs are isolated from the controller's dc supply, mixed ac and dc loads on different output groups are normal practice; keep the per-common current limit in mind when several contactor coils share a common terminal.
The analog inputs on all MicroLogix 1100 catalogue numbers are the same block: 0...10 V dc, 10-bit resolution with 0...+1,023 counts, 210 kΩ input impedance, ±0.5% of full scale accuracy from -20...+65 °C, and overvoltage protection at 10.5 V dc. They are not isolated from logic, and on this ac-powered variant the sensor supply common is internally connected to chassis ground - the documentation is explicit that the 24 V dc sensor supply must not be used to power output circuits, only input devices, so do not tap it for solenoids.
We Could Supply Full Range Of PLC Module.
If you find the PLC Module part that you are looking for, pls Skype / Email us for a quote.
Supports up to 144 digital I/O points
For a like-for-like replacement, note the power variant first: an ac-fed cabinet needs the 1763-L16BWA or 1763-L16AWA, not the dc-powered 1763-L16DWD or 1763-L16BBB. Keep the 1763-BA battery on the spares shelf, since it maintains the real-time clock and retentive memory, and keep a 1763-MM1 memory module if programs are moved between machines. The 1763-NC01 cable covers the RS-232/485 combo port when Ethernet is not available on site.
Expansion stops at four 1762 series I/O modules; beyond that the 1762 and 1766 platforms are the documented route. All specifications quoted here come from the MicroLogix 1100 installation instructions 1763-IN001 and the catalogue data for the family.
Same-family catalog numbers: 1763-L16AWA, 1763-L16BBB, 1763-L16DWD. Each of those catalogue numbers has its own stock page on this store; this page covers what differs in the 1763 family.
Other variants, batteries, memory modules and expansion modules are listed on our Allen-Bradley MicroLogix 1100 1763 category page; availability and lead time are confirmed by email at sales@plc-vip.com.