Product Details:
Payment & Shipping Terms:
|
| 1764-24AWA | MicroLogix 1500 24 Point Controller | IN STOCK |
| 1764-24BWA | MicroLogix 1500 24 Point Controller | IN STOCK |
| 1764-28BXB | MicroLogix 1500 28 Point Controller | IN STOCK |
| 1764-28BXB1 | MicroLogix 1500 28 Point Controller | IN STOCK |
| 1764-DAT | MicroLogix 1500 Data Access Tool | IN STOCK |
| 1764-LRP | MicroLogix 1500 Processor | IN STOCK |
| 1764-LSP | MicroLogix 1500 Processor | IN STOCK |
| 1764-MM1 | MicroLogix 1500 Memory Module | IN STOCK |
| 1764-MM1RTC | MicroLogix 1500 with RTC Memory Module | IN STOCK |
| 1764-MM2 | MicroLogix 1500 Memory Module | IN STOCK |
| 1764-MM2RTC | MicroLogix 1500 with RTC Memory Module | IN STOCK |
| 1764-MM3 | MicroLogix 1500 Memory Module | IN STOCK |
| 1764-MM3RTC | MicroLogix 1500 with RTC Memory Module | IN STOCK |
| 1764-RPLCDR1 | MicroLogix 1500 Replacement Part | IN STOCK |
| 1764-RPLTB1 | MicroLogix Replacement Part | IN STOCK |
| 1764-RPLTB2 | MicroLogix Replacement Part | IN STOCK |
| 1764-RTC | MicroLogix 1500 Real Time Clock | IN STOCK |
The 1764-LRP is the enhanced processor for the MicroLogix 1500 platform. It seats on any 1764 base unit - 1764-24AWA, 1764-24BWA or 1764-28BXB - and is the version that carries two RS-232 channels rather than one, plus Data Carrier Detect support that the standard 1764-LSP does not provide.
Two serial ports are the practical difference in the field. Channel 0 typically runs DF1 to a programming terminal or an operator panel, while Channel 1 carries ASCII to a weigh scale, a barcode reader or a printer, or a second DF1 link to another controller. On the 1764-LSP the same work has to share one port. Both channels can be selected for ASCII protocol on this processor, which is stated explicitly in the user manual.
It is a processor, not a controller: without a base unit it has no I/O and no supply. Buyers replacing a failed 1500 usually need the processor and the base separately, so confirm both catalogue numbers before ordering.
|
Brand Name
|
PLC Module
|
|
Cat Num
|
1764-LRP
|
|
Class
|
Central processing unit CPU processors
|
|
Communication
|
DF1 full/half duplex, DH-485, Modbus RTU slave, ASCII |
|
Communication Ports
|
2 (CH0 and CH1, both RS-232) |
|
Display
|
No
|
|
Enclosure
|
IP20
|
|
Interface
|
Isolated RS-232 port CH0, RS-232 port CH1 |
|
Memory
|
8K built-in (1764-MM2/MM2RTC required for programs over 8K) |
|
Memory Size
|
8K built-in, 8K or 16K with memory module |
|
Operating Temperature
|
0... 55 ?C (32...131 ?F)
|
|
Standard
|
C-TICK,GOST,KC,MARINE
|
|
Sub Brand
|
MicroLogix 1500
|
|
Type
|
Processor
|
|
UNSPSC
|
32151705
|
Program memory is the constraint to check first. The processor holds 8K, and the manual's own rule is that 1764-LRP programs greater than 8K require the 1764-MM2 or 1764-MM2RTC memory module. Memory modules come in 8K (1764-MM1, 1764-MM1RTC) and 16K (1764-MM2, 1764-MM2RTC, 1764-MM3, 1764-MM3RTC); the MM3 versions have the same user memory as MM2 but can additionally store recipe data from the Data Log Queue, which is the only functional difference between them. A 1764-RTC module adds a real-time clock without memory.
Firmware history is documented in the same manual: the 1764-LRP was released in March 2000 as series B with FRN 4 and, at that release, the same functionality as the 1764-LSP; the series C release in September 2001 brought FRN 6 with floating-point data files, programmable limit switch, real-time clock adjust, absolute value, gray code, recipe and message support for the 1769-SDN scanner. Programming needs RSLogix 500 version 4.00.00 or later for series B and later parts, and 5.10.00 or later for the series C feature set.
Communication: DF1 full-duplex defaults are 19.2 kbaud, no parity, node 1, CRC error detection, 50-count ACK timeout at 20 ms increments; DF1 half-duplex and DH-485 are configured per channel, and Modbus RTU slave operation maps coils and registers into MicroLogix data files. Bus current draw is 380 mA against 300 mA for the 1764-LSP, which matters when the base is close to its backplane budget and an expansion module is planned.
We Could Supply Full Range Of PLC Module.
If you find the PLC Module part that you are looking for, pls Skype / Email us for a quote.
google-site-verification: googlea6e157c12385cd64.html
When replacing a 1764-LSP with an LRP, check three things: the base unit part number (the LRP fits all three 1764 bases), the memory module in use - an 8K program that ran on an MM1 may need an MM2 if the new program grows - and the second port's cabling, which is the whole reason for choosing this part.
All statements here are from the MicroLogix 1500 Programmable Controllers user manual, publication 1764-UM001. Firmware dates and FRN numbers are quoted from its release table.
Processors, base units and memory modules are on our Allen-Bradley MicroLogix 1500 1764 page. Quotes and lead times: sales@plc-vip.com.