Product Details:
Payment & Shipping Terms:
|
| 1764-24AWA | MicroLogix 1500 24 Point Controller | IN STOCK |
| 1764-24BWA | MicroLogix 1500 24 Point Controller | IN STOCK |
| 1764-28BXB | MicroLogix 1500 28 Point Controller | IN STOCK |
| 1764-28BXB1 | MicroLogix 1500 28 Point Controller | IN STOCK |
| 1764-DAT | MicroLogix 1500 Data Access Tool | IN STOCK |
| 1764-LRP | MicroLogix 1500 Processor | IN STOCK |
| 1764-LSP | MicroLogix 1500 Processor | IN STOCK |
| 1764-MM1 | MicroLogix 1500 Memory Module | IN STOCK |
| 1764-MM1RTC | MicroLogix 1500 with RTC Memory Module | IN STOCK |
| 1764-MM2 | MicroLogix 1500 Memory Module | IN STOCK |
| 1764-MM2RTC | MicroLogix 1500 with RTC Memory Module | IN STOCK |
| 1764-MM3 | MicroLogix 1500 Memory Module | IN STOCK |
| 1764-MM3RTC | MicroLogix 1500 with RTC Memory Module | IN STOCK |
| 1764-RPLCDR1 | MicroLogix 1500 Replacement Part | IN STOCK |
| 1764-RPLTB1 | MicroLogix Replacement Part | IN STOCK |
| 1764-RPLTB2 | MicroLogix Replacement Part | IN STOCK |
| 1764-RTC | MicroLogix 1500 Real Time Clock | IN STOCK |
The 1764-24BWA is the ac-powered 24-point base unit of the MicroLogix 1500. Line power is 85...265 V ac, the twelve inputs are 24 V dc sink/source, the twelve outputs are relay, and the base supplies 24 V dc user power at 400 mA for the field devices it reads.
A MicroLogix 1500 is not a single part number: it is a processor (1764-LSP standard or 1764-LRP enhanced) seated on a base unit. The base decides the supply, the input voltage and the output type, and only the 1764-28BXB base offers FET outputs - so a 24BWA system always switches through relay contacts, whatever processor is fitted.
That combination is what makes the 24BWA practical in an existing cabinet: no separate 24 V dc supply is needed for the sensor bank because the base provides 400 mA at 24 V dc, and no interposing relays are needed because the outputs are dry contacts. The usual alternative, 1764-24AWA, reads 120 V ac inputs instead; the 1764-28BXB is dc powered and adds FET outputs.
|
Base Units
|
MicroLogix 1500 Base 24V DC In / Relay Out / AC Power
|
|
Brand Name
|
PLC Module
|
|
Cat Num
|
1764-24BWA
|
|
Class
|
controller
|
|
Depth
|
87 mm
|
|
Enclosure
|
IP20
|
|
Height
|
5.4331 in
|
|
Input Signal
|
24V DC sink/source, 12 points |
|
Interface
|
RS-232 port (CH0) on the processor |
|
Mounting
|
DIN Rail, Panel Mount
|
|
Number Of Channels
|
12 I/P, 12 O/P |
|
Operating Temperature
|
0... 55 ?C (32...131 ?F)
|
|
Output Signal
|
Relay, 12 points |
|
Power Supply
|
85...265V AC line power (120/240V AC), 24V DC user power at 400 mA |
|
Special Features
|
2 HSC, Expandable up to 512 I/O
|
|
Standard
|
C-TICK,GOST,KC,MARINE
|
|
Sub Brand
|
MicroLogix 1500
|
|
Type
|
Controller Base
|
|
UNSPSC
|
32151705
|
|
Width
|
168 mm
|
The twelve 24 V dc inputs are split into two behaviour classes, and the difference matters for sensor selection. Inputs 0...7 are documented at a 10...30.0 V dc on-state range at 30 °C (10...26.4 V dc at 55 °C), with on-state current 2.0 mA at 10 V, 8.9 mA at 24 V and 12.0 mA at 30 V, 3.3 kΩ nominal impedance, and an operating frequency up to 20 kHz limited only by scan time. Inputs 8 and higher need 14...30.0 V dc at 30 °C (14...26.4 V dc at 55 °C), draw 2.5 mA at 14 V, 7.3 mA at 24 V and 12.0 mA at 30 V into 2.7 kΩ, and are rated to 1 kHz. Off-state is 0...5 V dc for both, leakage 1.5 mA minimum. A 24 V dc sensor with a wide saturation window belongs on 0...7; a switch or contactor auxiliary belongs on 8 and up.
Relay ratings per pole: 240 V ac at 7.5 A make / 0.75 A break with 2.5 A continuous (1800 VA / 180 VA), 120 V ac at 15 A make / 1.5 A break with 2.5 A continuous, 125 V dc at 0.22 A make / 1.0 A break at 28 VA. The publication's rule for dc applies here as well: make/break amperes are found by dividing 28 VA by the applied dc voltage, and below 48 V dc the rating cannot exceed 2 A. Current per common is 8 A, per controller 24 A at 150 V and 20 A at 240 V, and relay mechanical life is 20,000,000 cycles.
Isolation figures are published per path: power supply input to backplane and relay output group to backplane at 2596 V dc (265 V working voltage, IEC Class 2 reinforced), input group to backplane and group to group at 2145 V dc (75 V dc working voltage), and user 24 V output to backplane at 848 V dc (50 V working voltage). Terminal screws take 1.13 N·m (10 in-lb) rated, 1.3 N·m (12 in-lb) maximum. The base measures 138 x 168 x 87 mm, runs 0...55 °C ambient, and is IP20.
We Could Supply Full Range Of PLC Module.
If you find the PLC Module part that you are looking for, pls Skype / Email us for a quote.
Fit a 1764-LSP or 1764-LRP processor, add a 1764-MM1/MM2 or RTC memory module if the program needs to be portable or time-stamped, and extend with 1769 Compact I/O to the right - the platform is expandable to 512 I/O. The 1764-DAT data access tool, 1764-RPL-TB1 terminal block and 1764-RPL-DR door kit are the common support parts.
Every figure on this page comes from the MicroLogix 1500 Programmable Controller Base Units installation instructions, publication 1764-IN001C-EN-P (June 2015), and the 1764-UM001 user manual. No value is estimated.
Same-family catalog numbers: 1764-24AWA. Each of those catalogue numbers has its own stock page on this store; this page covers what differs in the 1764 family.
Base units, processors, memory modules and 1769 expansion I/O are listed on our Allen-Bradley MicroLogix 1500 1764 category page. Quotes: sales@plc-vip.com.