Product Details:
Payment & Shipping Terms:
|
| 1766-L32AWA | 32 PT ML1400 AC IN/RELAY OUT | IN STOCK |
| 1766-L32AWAA | Mi32 PT ML 1400 AC IN/RELAY OUT/ANALOG IO | IN STOCK |
| 1766-L32BWA | 32PT ML 1400 DC IN RELAY OUT | IN STOCK |
| 1766-L32BWAA | Mi32 PT ML1400DC IN/RELAY OUT W ANALOG IO | IN STOCK |
| 1766-L32BXB | 32 PT ML1400 DC IO/RELAY OUT W ANALOG IO | IN STOCK |
| 1766-L32BXBA | 32 PT ML1400 DC IO/RELAY OUT W ANALOG IO | IN STOCK |
| 1766-MM1 | MicroLogix 1400 Memory Module | IN STOCK |
The 1766-L32BXB is the discrete-only member of the dc-powered MicroLogix 1400 pair. It runs from 24 V dc, reads 20 discrete 24 V dc inputs (12 fast and 8 standard), and drives 12 outputs made up of 6 relay, 3 fast 24 V dc FET and 3 standard 24 V dc FET. There is no analog block on this catalogue number.
That makes it the part for machines that are purely discrete: indexing, clamping, sorting, conveyor diverting, where every signal is a switch or a valve and nothing needs a 0...10 V loop. Compared with the 1766-L32BXBA, which shares the same supply and I/O arrangement but adds 4 analog inputs and 2 analog outputs, the BXB is the leaner unit for a panel that will never use analog - and it is the catalogue number to specify when a drawing already calls for BXB, since mixing the two changes the terminal layout.
The ac-fed equivalents in the same family are the 1766-L32BWA and 1766-L32BWAA (24 V dc inputs, 12 relay outputs), while 1766-L32AWA and 1766-L32AWAA read 120 V ac inputs. Choosing between them is a matter of panel supply and field voltage, not of program capability.
|
Brand Name
|
PLC Module
|
|
Cat Num
|
1766-L32BXB
|
|
Class
|
Programmable Logic Controller Accessories
|
|
Communication
|
DF1, DH-485, Modbus RTU, ASCII, DNP3, EtherNet/IP messaging, DNP3 over IP, Modbus TCP/IP
|
|
Depth
|
87 mm
|
|
Display
|
Yes
|
|
Embedded Analog
|
None |
|
Enclosure
|
IP20
|
|
Height
|
90 mm
|
|
Input Signal
|
24V DC (12 fast + 8 standard) |
|
Interface
|
EtherNet/IP port, isolated RS-232/RS-485 combo port, non-isolated RS-232 (D-sub) |
|
Memory
|
20 KB
|
|
Mounting
|
DIN Rail, Panel Mount
|
|
Number Of Channels
|
20 I/P, 12 O/P |
|
Operating Temperature
|
-20... 60 ?C (-4...140 ?F)
|
|
Output Signal
|
(6) Relay, (3) fast 24V DC FET, (3) standard 24V DC FET |
|
Power Supply
|
24V DC |
|
Special Features
|
Built-in RTC, Online Editing, 6 HSC, 3 PTO/PWM, Up to 7 Expansion I/O
|
|
Standard
|
C-TICK,GOST,KC,MARINE
|
|
Sub Brand
|
MicroLogix 1400
|
|
Type
|
Controller
|
|
UNSPSC
|
32151705
|
|
Width
|
180 mm
|
The output block is documented in 1766-IN001 as 6 relay outputs plus 3 fast 24 V dc FET and 3 standard 24 V dc FET. Relay ratings are 240 V ac 7.5 A make / 0.75 A break with 2.5 A continuous (1800 VA / 180 VA), 120 V ac 15.0 A make / 1.5 A break with 2.5 A continuous, 250 V dc 0.11 A make / 1.0 A break at 28 VA, and 125 V dc 0.22 A make / 1.0 A break at 28 VA, with 10 mA minimum load and 10 ms maximum switching time. Maximum controlled load for this catalogue number is 1080 VA, the same as the BXBA and lower than the 1440 VA all-relay versions.
The practical wiring rule is that the two output technologies do not mix electrically. The relay channels need a load reference supplied by the field circuit; the FET channels switch 24 V dc and share the controller's dc reference, and on the dc-powered controller the VDC NEUT terminal is internally tied to chassis ground. Grouping the relay outputs on the ac side of the panel and the FET outputs on the dc side, with separate commons, is the arrangement the terminal-block layout supports.
Inputs are 12 fast and 8 standard, all 24 V dc, on removable terminal blocks rated for 0.25...2.5 mm² (22...14 AWG) solid or 0.25...1.5 mm² (22...16 AWG) stranded Cu-90 °C wire at 0.791 N·m (7 lb·in). Because this controller has no analog block, the analog input terminals are absent rather than disabled - a panel drawing copied from a BXBA sheet will not map cleanly, and that is the single most common mistake when the two parts are substituted.
We Could Supply Full Range Of PLC Module.
If you find the PLC Module part that you are looking for, pls Skype / Email us for a quote.
The supporting list is short: 1766-MM1 memory module for program transfer, 1762 expansion modules up to seven per controller, and the programming cables for the non-isolated RS-232 port and the isolated RS-232/485 combo port. Ethernet on board covers normal program download and online monitoring.
If a future machine upgrade needs analog, plan the swap to the BXBA rather than adding external analog hardware, and check the terminal layout at that time. All specifications on this page are taken from the MicroLogix 1400 installation instructions 1766-IN001.
Same-family catalog numbers: 1766-L32AWA, 1766-L32AWAA, 1766-L32BWA, 1766-L32BWAA. Each of those catalogue numbers has its own stock page on this store; this page covers what differs in the 1766 family.
Controllers, memory modules and expansion I/O across the platform are listed on our Allen-Bradley MicroLogix 1400 1766 page. Quotes and lead times: sales@plc-vip.com.