Product Details:
Payment & Shipping Terms:
|
| 1766-L32AWA | 32 PT ML1400 AC IN/RELAY OUT | IN STOCK |
| 1766-L32AWAA | Mi32 PT ML 1400 AC IN/RELAY OUT/ANALOG IO | IN STOCK |
| 1766-L32BWA | 32PT ML 1400 DC IN RELAY OUT | IN STOCK |
| 1766-L32BWAA | Mi32 PT ML1400DC IN/RELAY OUT W ANALOG IO | IN STOCK |
| 1766-L32BXB | 32 PT ML1400 DC IO/RELAY OUT W ANALOG IO | IN STOCK |
| 1766-L32BXBA | 32 PT ML1400 DC IO/RELAY OUT W ANALOG IO | IN STOCK |
| 1766-MM1 | MicroLogix 1400 Memory Module | IN STOCK |
The 1766-L32BXBA is the dc-powered MicroLogix 1400 that carries the analog block. It runs from a 24 V dc input supply, reads 20 discrete 24 V dc inputs (12 fast and 8 standard), and drives 12 outputs arranged as 6 relay, 3 fast 24 V dc FET and 3 standard 24 V dc FET. On top of that it provides 4 voltage analog inputs and 2 voltage analog outputs, giving 32 discrete points and an analog channel set in one brick.
Inside the family the split is worth stating plainly, because catalogue numbers look similar and behave differently. The 1766-L32AWA and 1766-L32AWAA are ac powered and read 120 V ac inputs; the 1766-L32BWA and 1766-L32BWAA are ac powered but read 24 V dc; the 1766-L32BXB and 1766-L32BXBA are dc powered and read 24 V dc. The difference between BXB and BXBA is the analog block: BXBA has it, BXB does not. Both dc-powered variants share the same mixed output arrangement of 6 relay plus 6 FET, which is unusual for a compact controller and is the reason these two parts stay in service on machines that need both contact and solid-state switching.
So this part is the right choice when the panel is dc fed, the field devices are 24 V dc, at least one loop needs a 0...10 V analog signal in each direction, and the load list mixes ac contactors with dc valves. If no analog is needed, the BXB is the cheaper equivalent; if the panel is ac fed, BWAA or AWAA cover it.
|
Brand Name
|
PLC Module
|
|
Cat Num
|
1766-L32BXBA
|
|
Class
|
Programmable Logic Controller Accessories
|
|
Communication
|
DF1, DH-485, Modbus RTU, ASCII, DNP3, EtherNet/IP messaging, DNP3 over IP, Modbus TCP/IP
|
|
Depth
|
87 mm
|
|
Display
|
Yes
|
|
Embedded Analog
|
(4) Voltage Inputs / (2) Voltage Outputs, 12-bit |
|
Enclosure
|
IP20
|
|
Height
|
90 mm
|
|
Input Signal
|
24V DC (12 fast + 8 standard) |
|
Interface
|
EtherNet/IP port, isolated RS-232/RS-485 combo port, non-isolated RS-232 (D-sub) |
|
Memory
|
20 KB
|
|
Mounting
|
DIN Rail, Panel Mount
|
|
Number Of Channels
|
20 I/P, 12 O/P |
|
Operating Temperature
|
-20... 60 ?C (-4...140 ?F)
|
|
Output Signal
|
(6) Relay, (3) fast 24V DC FET, (3) standard 24V DC FET |
|
Power Supply
|
24V DC |
|
Special Features
|
Built-in RTC, Online Editing, 6 HSC, 3 PTO/PWM, Up to 7 Expansion I/O
|
|
Standard
|
C-TICK,GOST,KC,MARINE
|
|
Sub Brand
|
MicroLogix 1400
|
|
Type
|
Controller
|
|
UNSPSC
|
32151705
|
|
Width
|
180 mm
|
Publication 1766-IN001 groups the inputs as 12 fast 24 V dc inputs and 8 standard 24 V dc inputs across 20 points, wired on removable terminal blocks with 0.25...2.5 mm² (22...14 AWG) solid or 0.25...1.5 mm² (22...16 AWG) stranded Cu-90 °C conductors, torqued to 0.791 N·m (7 lb·in). On-state and off-state windows follow the 24 V dc input specification for the platform; the terminal layout drawing in the same publication shows the COM grouping, which is what matters when sinking sensors and sourcing sensors are mixed on one machine.
The output side is the documented mix: 6 relay outputs plus 3 fast 24 V dc FET and 3 standard 24 V dc FET. Relay contacts are rated 240 V ac at 7.5 A make / 0.75 A break with 2.5 A continuous and 1800 VA / 180 VA, at 120 V ac 15.0 A make / 1.5 A break with 2.5 A continuous, at 250 V dc 0.11 A make / 1.0 A break at 28 VA, and at 125 V dc 0.22 A make / 1.0 A break at 28 VA; minimum load current is 10 mA and switching time is 10 ms maximum. For this catalogue number the maximum controlled load is 1080 VA, against 1440 VA for the all-relay ac-powered versions - the FET channels are current-limited devices rather than dry contacts, so the two output types must not be paralleled or treated as interchangeable in a panel drawing.
The analog block on this part is 4 single-ended voltage inputs and 2 single-ended voltage outputs on a 0...10 V dc range, 12-bit unsigned integer data (0...4,095 counts), input impedance above 199 kΩ, non-linearity and overall accuracy ±1.0% of full scale from -20...+60 °C, input overvoltage protection at 10.5 V dc, output load range 1 kΩ, output settling 3 ms maximum and 2.5 ms step response at 95%. Field wiring is non-isolated from internal logic, and the documented maximum cable length for analog runs is 30 m (98 ft) shielded. That 12-bit, ±1.0% figure is a full two bits coarser than the MicroLogix 1100 analog block - if a loop needs better than that, the analog channel belongs in an external module, not on this brick.
We Could Supply Full Range Of PLC Module.
If you find the PLC Module part that you are looking for, pls Skype / Email us for a quote.
Supporting items on this platform are the 1766-MM1 memory module, the 1762 expansion I/O range (up to seven modules on a 1400 series controller), and the programming cables for the RS-232 port and the isolated RS-232/485 combo port. Because the controller carries Ethernet, program transfer and online monitoring normally run over the EtherNet/IP port, and the serial ports stay free for a panel HMI or a legacy DH-485 link.
Commissioning order that matches the hardware: confirm the 24 V dc supply and the input commons first, force the six relay outputs against the contactor list, then verify the six FET outputs against dc loads, and only then scale the analog channels - the input range is fixed 0...10 V dc with no jumper selection, so scaling is done in the program. Every specification on this page is taken from the MicroLogix 1400 installation instructions 1766-IN001; no value is estimated.
Same-family catalog numbers: 1766-L32AWA, 1766-L32AWAA, 1766-L32BWA, 1766-L32BWAA. Each of those catalogue numbers has its own stock page on this store; this page covers what differs in the 1766 family.
Other MicroLogix 1400 catalogue numbers, memory modules and 1762 expansion modules are listed on our Allen-Bradley MicroLogix 1400 1766 page. Availability and pricing: sales@plc-vip.com.