Product Details:
Payment & Shipping Terms:
|
| 1766-L32AWA | 32 PT ML1400 AC IN/RELAY OUT | IN STOCK |
| 1766-L32AWAA | Mi32 PT ML 1400 AC IN/RELAY OUT/ANALOG IO | IN STOCK |
| 1766-L32BWA | 32PT ML 1400 DC IN RELAY OUT | IN STOCK |
| 1766-L32BWAA | Mi32 PT ML1400DC IN/RELAY OUT W ANALOG IO | IN STOCK |
| 1766-L32BXB | 32 PT ML1400 DC IO/RELAY OUT W ANALOG IO | IN STOCK |
| 1766-L32BXBA | 32 PT ML1400 DC IO/RELAY OUT W ANALOG IO | IN STOCK |
| 1766-MM1 | MicroLogix 1400 Memory Module | IN STOCK |
The 1766-L32BWAA takes its input power from a 100/240 V ac supply, provides 24 V dc user power for field devices, reads 20 discrete 24 V dc inputs (12 fast and 8 standard), and switches 12 relay outputs - all of them dry contacts. It also carries 4 voltage analog inputs and 2 voltage analog outputs.
This is the variant that suits an existing ac-fed panel with modern dc sensors: no separate 24 V dc power supply is needed for the inputs because the controller supplies 24 V dc user power, and no interposing relay card is needed on the output side because all twelve outputs are relay. Where the loads are mostly dc valves and fast cycling is required, the dc-powered 1766-L32BXBA or 1766-L32BXB with their FET channels are the better fit; where the field devices are 120 V ac, the 1766-L32AWA and 1766-L32AWAA read them directly.
The housing is the standard MicroLogix 1400 brick: DIN rail or panel mount, IP20, -20...60 °C, 180 mm wide, 90 mm high, 87 mm deep, with an integrated display and keypad for address setting and immediate I/O status.
|
Brand Name
|
PLC Module
|
|
Cat Num
|
1766-L32BWAA
|
|
Class
|
Programmable Logic Controller Accessories
|
|
Communication
|
DF1, DH-485, Modbus RTU, ASCII, DNP3, EtherNet/IP messaging, DNP3 over IP, Modbus TCP/IP
|
|
Depth
|
87 mm
|
|
Display
|
Yes
|
|
Embedded Analog
|
(4) Voltage Inputs / (2) Voltage Outputs, 12-bit |
|
Enclosure
|
IP20
|
|
Height
|
90 mm
|
|
Input Signal
|
24V DC (12 fast + 8 standard) |
|
Interface
|
EtherNet/IP port, isolated RS-232/RS-485 combo port, non-isolated RS-232 (D-sub) |
|
Memory
|
20 KB
|
|
Mounting
|
DIN Rail, Panel Mount
|
|
Number Of Channels
|
20 I/P, 12 O/P |
|
Operating Temperature
|
-20... 60 ?C (-4...140 ?F)
|
|
Output Signal
|
(12) Relay |
|
Power Supply
|
120/240V AC (100/240V AC input power) |
|
Special Features
|
Built-in RTC, Online Editing, 6 HSC, Up to 7 Expansion I/O
|
|
Standard
|
C-TICK,GOST,KC,MARINE
|
|
Sub Brand
|
MicroLogix 1400
|
|
Type
|
Controller
|
|
UNSPSC
|
32151705
|
|
Width
|
180 mm
|
Twelve relay outputs change the way a panel is drawn. Each output is a dry contact, so ac contactor coils, dc solenoids and signal-level circuits can sit on the same controller without external interface relays, and the isolation is inherent rather than dependent on the controller's internal supply. The documented contact ratings are 240 V ac at 7.5 A make / 0.75 A break with 2.5 A continuous (1800 VA / 180 VA), 120 V ac at 15.0 A make / 1.5 A break with 2.5 A continuous, 250 V dc at 0.11 A make / 1.0 A break at 28 VA, and 125 V dc at 0.22 A make / 1.0 A break at 28 VA, with 10 mA minimum load current and 10 ms maximum switching time. Maximum controlled load for this catalogue number is 1440 VA - the higher figure applies to the all-relay variants, while the FET-equipped dc-powered versions are rated 1080 VA.
The 20 discrete inputs are split 12 fast and 8 standard, all 24 V dc, with the terminal-block grouping shown in 1766-IN001 so that sinking and sourcing field devices can be separated by common. Wiring accepts 0.25...2.5 mm² (22...14 AWG) solid or 0.25...1.5 mm² (22...16 AWG) stranded Cu-90 °C conductors at 0.791 N·m (7 lb·in) torque.
The analog section is 4 voltage inputs on 0...10 V dc with 12-bit resolution (0...4,095 counts) and input impedance above 199 kΩ, plus 2 single-ended voltage outputs on the same range, 1 kΩ load, 3 ms maximum settling. Accuracy is ±1.0% of full scale over -20...+60 °C, overvoltage protection is 10.5 V dc, and analog wiring is non-isolated from logic with a documented 30 m (98 ft) shielded-cable limit. On an ac-powered controller this matters in practice: the analog commons and the controller's internal reference are one node, so grounded transmitters should be checked for a ground loop before the loop is trusted.
We Could Supply Full Range Of PLC Module.
If you find the PLC Module part that you are looking for, pls Skype / Email us for a quote.
For a like-for-like swap in an ac cabinet, this part and the 1766-L32AWAA are the two ac-powered options; BWA and BWAA read 24 V dc, AWA and AWAA read 120 V ac. Keep the 1766-MM1 memory module for program transfer and the 1762 expansion modules in mind: the 1400 platform accepts up to seven of them, which is the practical ceiling before a CompactLogix migration makes more sense.
Commissioning order: verify the ac supply and 24 V dc user power, force the twelve relay outputs against the actual coil list, then commission the analog channels with a calibrated 0...10 V source. All specifications quoted here come from the MicroLogix 1400 installation instructions 1766-IN001.
Same-family catalog numbers: 1766-L32AWA, 1766-L32AWAA, 1766-L32BWA, 1766-L32BXB. Each of those catalogue numbers has its own stock page on this store; this page covers what differs in the 1766 family.
The full MicroLogix 1400 range, including the dc-powered BXB/BXBA, is on our Allen-Bradley MicroLogix 1400 1766 category page. Quotes: sales@plc-vip.com.