Product Details:
Payment & Shipping Terms:
|
| 1746-IA16 | SLC 16 Point Digital Input | IN STOCK |
| 1746-IA4 | SLC 4 Point Digital Input Module | IN STOCK |
| 1746-IA8 | SLC 8 Point AC Input Module | IN STOCK |
| 1746-IB16 | SLC 16 Point DC Input Module | IN STOCK |
| 1746-IB32 | SLC 32 Point DC Input Module | IN STOCK |
| 1746-IB8 | SLC 8 Point DC Input Module | IN STOCK |
| 1746-IC16 | SLC 16 Point Digital Input Module | IN STOCK |
| 1746-IG16 | SLC TTL Input Module | IN STOCK |
| 1746-IH16 | SLC 16 Point Digital Input Module | IN STOCK |
| 1746-IM16 | SLC 16 Point 240V AC Input Module | IN STOCK |
| 1746-IM4 | SLC 4 Point Digital Input Module | IN STOCK |
| 1746-IM8 | SLC 8 Point Digital Input Module | IN STOCK |
| 1746-IN16 | SLC 16 Point 24V AC Input Module | IN STOCK |
| 1746-INT4 | SLC 4 Point Thermocouple Module | IN STOCK |
| 1746-IO12 | SLC 12 Point Combination Module | IN STOCK |
| 1746-IO12DC | SLC 12 Point Combination Module | IN STOCK |
| 1746-IO4 | SLC 4 Point Combination Module | IN STOCK |
| 1746-IO8 | SLC 8 Point Combination Module | IN STOCK |
| 1746-ITB16 | SLC 16 Point Digital Input Module | IN STOCK |
| 1746-ITV16 | SLC 16 Point Digital Input Module | IN STOCK |
| 1746-IV16 | SLC 16 Point Digital Input Module | IN STOCK |
| 1746-IV32 | SLC 32 Point Digital Input Module | IN STOCK |
| 1746-IV8 | SLC 8 Point Digital Input Module | IN STOCK |
The 1746-IA16 is the 16-point 120 V ac input module for the SLC 500 chassis. It reads 85...132 V ac at 47...63 Hz on sixteen points that share a single common, and it is the module that lets a panel wire pushbuttons, limit switches, float switches and 120 V ac relay contacts straight into the controller with no interposing relays.
Its place in the 1746 input family is defined by voltage: 1746-IA4 and 1746-IA8 are the 4- and 8-point versions of the same 120 V ac circuit, 1746-IM16 is the 240 V ac counterpart, 1746-IB16 and 1746-IV16 cover 24 V dc sinking and sourcing, and 1746-IN16 handles 24 V ac/dc. Choosing between them is a field-voltage decision, not a function decision.
Sixteen points on one common is the detail that matters when planning a chassis: the whole module behaves as one input group, so a panel that needs separated commons for different voltage zones has to use the smaller IA4/IA8 modules or a dc module with isolated groups instead.
|
Brand Name
|
PLC Module
|
|
Cat Num
|
1746-IA16
|
|
Class
|
Programmable Logic Controller Module
|
|
Digital AC Input Modules
|
16 ch-AC Input Module For Programmable Controller
|
|
Display
|
Status Display
|
|
Enclosure
|
None (open-style)
|
|
Input Signal
|
85...132V AC, 47...63 Hz |
|
Isolation
|
1500V between I/O terminals and control logic (electro-optical) |
|
Module Type
|
digital
|
|
Mounting
|
Chassis
|
|
Number Of Channels
|
16 inputs, one common (16 points per common) |
|
Operating Temperature
|
0...60 C (32...140 F)
|
|
Special Features
|
Removable terminal block, 35 ms on / 45 ms off delay, 4.80 W total |
|
Standard
|
GOST,KC,MARINE
|
|
Sub Brand
|
SLC
|
|
Type
|
AC Input Module
|
|
UNSPSC
|
32151705
|
|
Voltage Rating
|
100/120V AC signal input |
Per the 1746 digital I/O specification, the operating window is 85...132 V ac at 47...63 Hz with a nominal input current of 12 mA at 120 V ac. Off-state voltage is 30 V ac maximum and off-state current 2 mA maximum, so a leaking proximity switch or a shared neutral with a solid-state device is visible as a false input rather than a mystery. Maximum inrush is 0.8 A - the publication warns that the field device must be compatible with that inrush and that a series resistor will limit it at the cost of changing the input's operating characteristics.
Signal delay is the number to plan cycle time around: 35 ms maximum on and 45 ms maximum off. That is a filtered, general-purpose ac input, suited to pushbuttons and level switches, not to capturing a 10 ms event. Backplane draw is 0.050 A at 5 V dc and 0 A at 24 V dc, heat dissipation is 4.80 W total (0.27 W per point with a 0.425 W minimum), and isolation between the I/O terminals and the control logic is 1500 V, electro-optical.
Module-level: 0...60 °C operating, -40...85 °C storage, 5...95% non-condensing humidity, operating shock 30 g, NEMA ICS 2-230 noise immunity, UL listed / CSA certified / CE compliant, and Class I Division 2 approval for this catalogue number. The 1746-IA16 has a removable terminal block - the IA4 and IA8 do not - which is what allows a module to be swapped without disturbing field wiring. Wiring diagrams in the publication carry both decimal and octal addressing, decimal for SLC systems and octal for PLC systems.
We Could Supply Full Range Of PLC Module.
If you find the PLC Module part that you are looking for, pls Skype / Email us for a quote.
If you have any questions, also pls Skype / Email us
.
Count the commons, not just the points. Because all 16 inputs share one common, a chassis that mixes 120 V ac signals from two different control transformers needs either separate modules or a single bonded reference. The 1746-IA8 (8 points, two groups of 4) is the usual answer when that separation is required.
All specifications here come from the SLC 500 Digital I/O Modules installation instructions, publication 1746-IN027. Values are quoted, not derived.
Same-family catalog numbers: 1746-IA4, 1746-IA8. Each of those catalogue numbers has its own stock page on this store; this page covers what differs in the 1746 family.
Other 1746 input and output modules are listed on our Allen-Bradley SLC 500 Systems 1746 category page. Availability: sales@plc-vip.com.